Install Refrigerant Pipe Insulation
Figure 19 shows typical pipe insulation. Insulate all field provided refrigerant pipes and cold surfaces according to these guidelines:
• Insulate all cold surfaces sufficiently to prevent moisture from forming on the surface. All pipes must be insulated and each pipe must
be wrapped separately.
• Use field-provided 1/2" thick (or more) closed cell insulation. The thickness may need to be increased based on ambient conditions
and local codes.
• All refrigerant a condensate piping including field-provided isolation ball valves and flexible pipe connection kits provided by LG should
be wrapped.
• All insulation joints should be glued with no air gaps between insulation segments and between insulation segments and the unit case.
Insulation material shall fit snugly against the refrigeration pipe with no air space between the pipe surface and the surrounding insula-
tion. See Figure 19.
• All pipe passing through pipe hangers, inside conduit, and/or sleeves must not be compressed. Protect insulation inside hangers and
supports with a second layer.
Insulation for Indoor Unit Port
(Field Supplied)
Insulation Clip (Field Supplied)
No Clearance
Figure 19: Typical Pipe Insulation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.

INSULATE PIPES

Insulation for Refrigerant
Piping (Field Supplied)
Overlap Insulation Where the
Port and the Piping Meet
21