Connecting Pipes To The Indoor Unit - LG GBUH186HSS0 Installation Manual

Concealed duct air conditioner
Table of Contents

Advertisement

Connecting Pipes to the Indoor Unit

Preparation of Piping
Main cause of gas leakage is defect in flaring
work. Carry out correct flaring work in the
following procedure.
Cut the pipes and the cable.
• Use the accessory piping kit or the pipes
purchased locally.
• Measure the distance between the indoor and
the outdoor unit.
• Cut the pipes a little longer than measured
distance.
• Cut the cable 1.5m longer than the pipe
length.
Burrs removal
• Completely remove all burrs from the cut cross
section of pipe/tube.
• Put the end of the copper tube/pipe to
downward direction as you remove burrs in
order to avoid to let burrs drop in the tubing.
Putting nut on
• Remove flare nuts attached to indoor and
outdoor units, than put them on pipe/tube
having completed burr removal.
(Not possible to put them on after flaring work)
Flaring work
• Carry out flaring work using flaring tool as
shown below.
Outside Diameter
6.35(1/4")
9.52(3/8")
12.70(1/2")
15.88(5/8")
19.05(3/4")
Firmly hold copper tube in a bar(or die) as
indicated dimension in the table above.
Check
• Compare the flared work with figure.
• If flare is noted to be defective, cut off the
flared section and do flaring work again.
Copper
"A"
1.1~1.3
1.5~1.7
1.6~1.8
1.6~1.8
1.9~2.1
Even length
Connecting Pipes to the Indoor Unit
tube
90°
Point down
Flare nut
Copper tube
Bar
Bar
"A"
Copper pipe
Clamp handle
Smooth all round
Inside is shiny without scratches
Inclined
all round
Slanted Uneven Rough
Pipe
Reamer
Handle
Yoke
Cone
Red arrow mark
= Improper flaring =
Surface
Cracked Uneven
damaged
thickness
Installation Manual 19

Advertisement

Table of Contents
loading

Table of Contents