Roughing In Overview; Location Selection - LG Multi V Installation Manual

Convertible surface mounted and ceiling suspended indoor units
Hide thumbs Also See for Multi V:
Table of Contents

Advertisement

ROUGHING IN
Overview

Location Selection

Refer to Figure 1 for clearance dimensions for the ceiling suspended unit. Refer to Figure 2 for clearance dimensions for the convertible unit,
both ceiling mounted and wall mounted.
Note:
The ceiling suspended unit and the ceiling mounted convertible unit have different clearance dimensions.
Choose a location that conforms to the following:
• The structure will support the weight of the unit and accessories.
• The mounting location is strong and solid enough to prevent vibrations.
• Allows the unit to easily be hung in a level position.
• Provides clearance around the unit considering refrigerant piping, condensate line installation, control panel, and major component
maintenance access.
• Is free from electrical noise caused by nearby generators and high voltage wiring.
• Is away from airborne sources of grease, steam, excessive heat, flammable substances, salt, and/or acidic vapors.
• Ambient airborne particulate is at nominal levels.
• Select a location with no obstacles in front of the unit and where the condensation drain pipe can be conveniently routed away.
• For the convertible unit, ensure there is a space of more than 7 7/8" between walls and the left and right sides. Also ensure there is a space
of more than 2" between the bottom of the unit and the wall or floor. If installing on a wall, position the unit as low on the wall as possible,
but more than 2" above the floor.
• For the ceiling suspended unit, ensure there is a space of more than 27 9/16" between walls and the left and right sides. Also ensure there
is a space of more than 11 3/16" between the rear of the unit and the wall.
• Do not install the unit near a source of heat or steam, in a doorway, or near high-frequency generators.
• Do not install where sulfurous acid gas or corrosive gas is generated.
• Do not install where cooking oil or iron powder are generated or where flammable gas is generated, flows, stored, or vented.
More than
27-9/16 inches
Figure 1: Ceiling Suspended Unit Clearance Dimensions.
12
More than
27-9/16 inches
More than
11-13/16 inches
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
More than
7-7/8 inches
More than
7-7/8 inches
More than
2 inches
Figure 2: Convertible Surface Mounted Unit Clearance Dimensions.
More than
7-7/8 inches
More than
2 inches
More than
7-7/8 inches