INDOOR UNIT CONTROL SETTINGS

Temperature Sensing Configuration
By default, the room temperature is sensed by the factory mounted return air thermistor. If an optional wall mounted zone controller is
present, the room temperature can be sensed by one of three methods.
• At the indoor unit return air sensor.
• At the wall-mounted zone controller.
• At both the return air thermistor and zone controller.
If the return air thermistor and zone controller method is chosen, the indoor unit does not average the readings. The indoor unit is controlled
using the reading that is farthest away from set point at a given time. Refer to the zone controller installation manual for detailed information
on setting the sensor control DIP switch.