8 Adapting the unit to the heating installation

Overview of diagnostics codes (→ Page 43)
Call up the Live Monitor.
Menu → Live Monitor
If the hot water generation is working correctly, S.24
appears in the display.
7.17
Thoroughly flushing the heating installation
("hot")
1.
Operate the appliance until the boiler and the heating
system are up to temperature.
2.
Check the heating system for leaks.
3.
Connect a hose to the drain valve located at the lowest
position of the heating system.
4.
Shut off the boiler, open the drain valve and all purge
valves on the radiators and allow the water to flow out
of the heating system and the boiler quickly and fully.
5.
Close the drain valve.
6.
Fill the heating system again with water as described in
Filling the heating installation (→ Page 24) and Purging
the heating installation (→ Page 24).
7.
Re-fill the system until the system design pressure of
0,1 MPa (1,0 bar) is attained.
Note
The actual reading on the digital pressure
gauge should ideally be 0,05 MPa (0,5 bar)
plus an additional pressure corresponding
to the highest point of the system above the
base of the boiler – 10 m head equals an ad-
ditional 1 bar reading on the pressure gauge.
The minimum pressure should not be less
than 0,1 MPa (1 bar) in any installation. If
the system is to be treated with an inhibitor it
should be applied at this stage in accordance
with the manufacturer's instructions. Further
information can be obtained from Sentinel,
Betz Dearborn Ltd., Tel: 0151 420 9595, or
Fernox, Alpha– Fry technologies. Tel: 0870
8700362.
8.
Install the front casing.
8
Adapting the unit to the heating
installation
To reset the most important system parameters, use the
Appliance config. menu point.
Menu → Installer level Appliance config.
Or manually relaunch the installation assistant.
Menu → Installer level → Start inst. assistant
You can find setting options in the Diagnostics menu.
Menu → Installer level Diagnostics menu
Overview of diagnostics codes (→ Page 43)
28
8.1

Burner anti-cycling time

To prevent frequent switching on and off of the burner and
thus prevent energy losses, an electronic restart lockout
is activated for a specific period each time the burner is
switched off. The burner anti-cycling time is only active
for the heating mode. Hot water handling during a burner
anti-cycling time does not affect the time function element
(default setting: 20 mins).
8.1.1
Setting the burner anti-cycling time
Navigate to Menu → Installer level → Diagnostics
1.
menu → D.002 Max. anti-cycl. time: Heating and con-
firm by pressing
.
2.
Set the burner anti-cycling time and confirm by pressing
.
T
Set maximum burner anti-cycling time [min]
Flow
(tar-
get)
1
5
[°C]
30
2.0
4.0
35
2.0
4.0
40
2.0
3.5
45
2.0
3.0
50
2.0
3.0
55
2.0
2.5
60
2.0
2.0
65
2.0
1.5
70
2.0
1.5
75
2.0
1.0
Set maximum burner anti-cycling time
T
Flow
[min]
(target)
[°C]
35
30
29.0
35
25.5
40
22.5
45
19.5
50
16.5
55
13.5
60
10.5
65
7.0
70
4.0
75
1.0
8.1.2
Resetting the remaining burner anti-cycling
time
1.
Alternatives 1 / 2
Navigate to Menu Reset anti-cycl. time.
The current burner anti-cycling time appears in
the display.
Press
to reset the burner anti-cycling time.
Alternatives 2 / 2
1.
Press
.
Installation and maintenance instructions ecoTEC plus 0020209593_01
10
15
20
25
8.5
12.5
16.5
20.5
7.5
11.0
15.0
18.5
6.5
10.0
13.0
16.5
6.0
8.5
11.5
14.0
5.0
7.5
9.5
12.0
4.5
6.0
8.0
10.0
3.5
5.0
6.0
7.5
2.5
3.5
4.5
5.5
2.0
2.5
2.5
3.0
1.0
1.0
1.0
1.0
40
45
50
55
33.0
37.0
41.0
45.0
29.5
33.0
36.5
40.5
26.0
29.0
32.0
35.5
22.5
25.0
27.5
30.5
18.5
21.0
23.5
25.5
15.0
17.0
19.0
20.5
11.5
13.0
14.5
15.5
8.0
9.0
10.0
11.0
4.5
5.0
5.5
6.0
1.0
1.0
1.0
1.0
30
25.0
22.0
19.5
17.0
14.0
11.5
9.0
6.5
3.5
1.0
60
49.5
44.0
38.5
33.0
28.0
22.5
17.0
11.5
6.5
1.0