Checking Function And Leak-Tightness - Vaillant ecoTEC plus Installation And Maintenance Instructions Manual

Table of Contents

Advertisement

Settings
CO₂ after 5 minutes
in full load mode with
front casing closed
CO₂ after 5 minutes
in full load mode with
front casing removed
Set for Wobbe index
W₀
O₂ after 5 minutes in
full load mode with
front casing closed
CO value with full load
CO/CO₂
Conditions: The CO₂ content must be adjusted
Pierce the covering cap (1) at the mark using a small
flat-blade screwdriver and unscrew it.
After performing the adjustments, tilt the air intake pipe
back up.
Check the CO₂ content again.
If necessary, repeat the setting process.
Set the CO₂ content (value with front casing removed)
by turning the screw (2).
Higher CO₂ content: Turn anti-clockwise
Lower CO₂ content: Turn clockwise
For natural gas only: Only perform the adjustment in in-
crements of 1 turn and wait approx. 1 minute after each
adjustment until the value stabilises.
For liquid gas only: Only perform the adjustment in small
increments (approx. 1/2 turn), and wait approx. 1 minute
after each adjustment until the value stabilises.
Check the CO₂ content again.
If necessary, repeat the setting process.
Press
(Cancel) once the adjustments have been
made.
0020209593_01 ecoTEC plus Installation and maintenance instructions
Unit
G20
G31 liquid
natural
gas
gas
9.2 ± 1.0
10.4 ± 0.5
Vol.–%
9.0 ± 1.0
10.2 ± 0.5
Vol.–%
kWh/m³
14.09
21.34
4.5 ± 1.8
5.1 ± 0.8
Vol.–%
≤ 250
≤ 250
ppm
≤ 0.0031
≤ 0.0026
If an adjustment is not possible in the specified adjust-
ment range, you must not start up the product.
If this is the case, inform Customer Service.
Screw the covering cap back in.
Install the front casing.
7.16

Checking function and leak-tightness

Before you hand the product over to the operator:
Check the gas line, the flue gas installation, the heating
installation and the hot water pipes for leaks.
Check that the air/flue pipe and condensate drain pipe-
work have been installed correctly.
Check that the front casing has been installed correctly.
7.16.1 Checking the heating mode
1.
Make sure that there is a heat requirement.
2.
Call up the Live Monitor.
If the product is working correctly, the display shows
S.04.
1
7.16.2 Checking the hot water generation
1.
Open a hot water valve all the way.
2.
Call up the Live Monitor.
If the hot water generation is working correctly, S.14
appears in the display.
7.16.3 Checking the cylinder charging
Note
2
Cylinder charging is deactivated ex-works and
must be activated during initial start-up.
The cylinder charging of the shift-load cylinder is only active
if Comfort mode is switched on. If Comfort mode is activated,
the symbol "C" appears in the display ( Operating instruc-
tions).
When cylinder charging is switched on, the following temper-
atures can be set for the hot water temperature (see operat-
ing instructions):
Minimum temperature 50 °C
Maximum temperature 65 °C
When cylinder charging is switched off, the following temper-
atures can be set for the hot water temperature:
Minimum temperature 35 °C
Maximum temperature 65 °C
If cylinder charging is switched off, the cylinder is not held
at temperature. If you draw off water, the boiler switches on
and, in this case, only operates on the through-flow principle.
The product is equipped with an automatic Anti-legionella
function; if the temperature in the domestic hot water
cylinder falls below 50 °C, the cylinder is heated up to
70 °C once every 24 hours. If required, in consultation
with the operator, switch the Anti-legionella function off
using diagnostics code D.074.
Start-up 7
27