Service
Information about the installation
E59 - Inverter error
Disconnect the outdoor fan motor
connector and try to startup
Does compressor startup?
NO
Is power supply voltage OK?
YES
Is the pressure balance at starting
OK?
YES
Is the insulation resistance and coil
resistance of compressor OK?
YES
Is power transistor module OK?
YES
Is the inverter output OK?
YES
Try to startup several times.
Can start?
YES
NO
Check power supply.
Check refrigerant amount and
NO
refrigerant circuit.
NO
NO
NO
Note: Several times restarting trial may
make a recovery from startup failure,
because liquid refrigerant migrated in the
compressor could be discharged during
several trial.
NO
- 132 -