E59 - Inverter Error - Mitsubishi Heavy Industries FDCW100VNX Technical Manual

Air to water heat pump
Hide thumbs Also See for FDCW100VNX:
Table of Contents

Advertisement

Service
Information about the installation

E59 - Inverter error

Disconnect the outdoor fan motor
connector and try to startup
Does compressor startup?
NO
Is power supply voltage OK?
YES
Is the pressure balance at starting
OK?
YES
Is the insulation resistance and coil
resistance of compressor OK?
YES
Is power transistor module OK?
YES
Is the inverter output OK?
YES
Try to startup several times.
Can start?
YES
NO
Check power supply.
Check refrigerant amount and
NO
refrigerant circuit.
NO
NO
NO
Note: Several times restarting trial may
make a recovery from startup failure,
because liquid refrigerant migrated in the
compressor could be discharged during
several trial.
NO