Mitsubishi Heavy Industries FDCM100VNX-W User Manual

Mitsubishi Heavy Industries FDCM100VNX-W User Manual

Air to water heat pump
Hide thumbs Also See for FDCM100VNX-W:

Advertisement

Quick Links

USER'S MANUAL
AIR TO WATER HEAT PUMP
Hydrolution EZY
FDCM100/140VNX-W
PT300/PT500/RC-HY20-W/RC-HY40-W
This heat pump complies with EMC Directive 2014/30/EU,
LV Directive 2014/35/EU.
CE marking is applicable to the area of 50 Hz power supply.
This heat pump complies with EMC S.I. 2016/1091, EER S.I.
2016/1101.
UKCA marking is applicable to the area of 50Hz power
supply.
Cette pompe à chaleur est conforme à la directive
CEM 2014/30/UE et la directive BT 2014/35/UE.
Le marquage CE est applicable à la zone d'alimentation
électrique de 50 Hz.
Diese Wärmepumpe erfüllt die EMV-Richtlinie 2014/30/EU
und die Niederspannungsrichtlinie 2014/35/EU.
Die CE-Kennzeichnung gilt für die Gebiete mit einer
Stromversorgung mit 50 Hz.
Questa pompa di calore è conforme alla direttiva EMC
2014/30/UE, direttiva Bassa tensione 2014/35/UE.
Il marchio CE è applicabile all'area di alimentazione a 50 Hz.
USER'S MANUAL
AIR TO WATER HEAT PUMP
MANUEL DE L'UTILISATEUR
POMPE À CHALEUR AIR/EAU
BENUTZERHANDBUCH
LUFT-WASSER-WÄRMEPUMPE
MANUALE DELL'UTENTE
POMPA DI CALORE ARIA-ACQUA
MANUAL DE USUARIO
BOMBA DE CALOR AIRE/AGUA
GEBRUIKERSHANDLEIDING
LUCHT-WATERWARMTEPOMP
MANUAL DO UTILIZADOR
BOMBA DE CALOR AR/ÁGUA
KULLANICI KILAVUZU
HAVADAN SUYA ISI POMPASI
English:Original instruction
Others : Translation of the original instruction
Esta bomba de calor cumple con la Directiva 2014/30/UE
de CEM, Directiva 2014/35/UE de BT.
El marcado CE aplica al area con fuente de alimentación
en 50 Hz.
Deze warmtepomp voldoet aan EMC-richtlijn 2014/30/EU,
laagspanningsrichtlijn 2014/35/EU.
De CE-markering is van toepassing op gebieden met 50 Hz
netvoeding.
Esta bomba de calor está em conformidade com a Diretiva
CEM 2014/30/UE e Diretiva LV 2014/35/UE.
A marcação CE é aplicável à área de fonte de alimentação
de 50 Hz.
Bu ısı pompası Elektromanyetik Uyumluluk (EMC)
Direktifi 2014/30/EU, LV Direktifi 2014/35/EU ile uyumludur.
CE işareti 50 Hz güç kaynağı alanı için geçerlidir.
ORIGINAL INSTRUCTIONS
ENGLISH
FRANÇAIS
DEUTSCH
ITALIANO
ESPAN ˜ OL
NEDERLANDS
PORTUGUÊS
TÜRKÇE
PSB012A025A
202312

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FDCM100VNX-W and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Mitsubishi Heavy Industries FDCM100VNX-W

  • Page 1 ORIGINAL INSTRUCTIONS USER’S MANUAL AIR TO WATER HEAT PUMP USER’S MANUAL ENGLISH Hydrolution EZY AIR TO WATER HEAT PUMP FDCM100/140VNX-W MANUEL DE L’UTILISATEUR FRANÇAIS PT300/PT500/RC-HY20-W/RC-HY40-W POMPE À CHALEUR AIR/EAU BENUTZERHANDBUCH DEUTSCH LUFT-WASSER-WÄRMEPUMPE MANUALE DELL’UTENTE ITALIANO POMPA DI CALORE ARIA-ACQUA ESPAN ˜ OL MANUAL DE USUARIO BOMBA DE CALOR AIRE/AGUA GEBRUIKERSHANDLEIDING...
  • Page 2 ● Compatibility Compatible Controller (RC-HY) Outdoor unit FDCM100VNX-W FDCM140VNX-W RC-HY20-W Controller RC-HY40-W...
  • Page 3: Table Of Contents

    Table of Contents Safety precautions General     Installation data   6 ENGLISH  6 Serial number  RC-HY20/40-W-An excellent choice   7 Quick guide     FRANÇAIS The controller the heart of the house     Controller function   8  8 Contact with RC-HY20/40-W  Maintenance of RC-HY20/40-W ...
  • Page 4: Safety Precautions

    Safety precautions SAFETY PRECAUTIONS Please read these “SAFETY PRECAUTIONS” the system, make sure to pass this before starting to use this product and use manual. This heat pump complies with the product appropriately according to the EMC Directive 2014/30/EC and EMC S.I. instructions.
  • Page 5 Safety precautions The appliance shall be stored in a well- OPERATION PRECAUTIONS ventilated area where the room size DANGER corresponds to the room area as specified Do not expose yourself directly to for operation. radiator or any other heating device The staff in servicing operations must for a long time.
  • Page 6 Safety precautions Do not place any other electric appliances CAUTION or household goods below or around the Do not use for particular purpose such air conditioner. as the storage of food, animals and plants, precision apparatus and arts etc. Leakage from the unit may lead to failure or contamination.
  • Page 7 Safety precautions Do not operate or stop the unit by Before repairing or checking the using the power supply switch. outdoor unit, be sure to turn off “outdoor unit power supply breaker”. It may lead to fire or water leakage. If auto restart is set effectively, the fan It can result in electric shock or injury may rotate suddenly causing injuries.
  • Page 8: General

    General General Hydrolution EZY is a system for heating, cooling and producing hot water for small houses. The system consists of an outdoor unit and a controller that supply and control the heat distribution in the house. NOTE This Product contains fluorinated greenhouse gases. Do not vent R32 into the atmosphere: R32 is a fluorinated greenhouse gas with a Global Warming Potential (GWP) = 675.
  • Page 9: Rc-Hy20/40-W-An Excellent Choice

    General / Quick guide Quick guide Navigation Serial number Ok button (confirm/select) Control knob (move/increase/reduce) Back button (back/undo/exit) page 8. How to scroll through menus and make different settings is Set the indoor climate TEMPERATURE HEATING 1.1.1 30ºC 20ºC INDOO R CLIM ATE 10ºC HOT WATER MYINS TALL ATION...
  • Page 10: The Controller The Heart Of The House

    The controller – the heart of the house B Status lamp The controller – the heart of the house Controller function C OK button the start guide. Contact with RC-HY20/40-W D Back button Display unit Display E Control knob Status lamp OK button Back button Control knob...
  • Page 11 The controller – the heart of the house Menu system Symbols in the display The menu system’s four main menus are shown in the display The following symbols can appear in the display during as well as certain basic information. operation.
  • Page 12 The controller – the heart of the house Menu number – marked sub menu Name and menu number – main menu Symbol – main menu INDOOR CLIMATE 1 temperature 25.0 INDOO R CLIM ATE scheduling HOT WATER MYINS TALL ATION advanced INFO Marked main menu...
  • Page 13 The controller – the heart of the house Use the virtual keyboard Help menu 1.   2.   Different keyboards scroll between using the control knob. Depending on the menu, you can gain access to different character sets which you can select using the control knob. To has one character set, the keyboard is displayed directly.
  • Page 14: Maintenance Of Rc-Hy20/40-W

    The controller – the heart of the house Maintenance of RC-HY20/40-W Equipment Normal Output Approx. annual con- Regular checks sump- tion Your heat pump requires minimal maintenance after (kWh) Opera- Standby check your installation regularly. For more information tion If something unusual occurs, messages about the malfunction alarm management on page 36.
  • Page 15: Rc-Hy20/40-W - At Your Service

    RC-HY20/40-W – at your service Menu 1.1 - temperature RC-HY20/40-W – at your service Set the indoor climate the display by a thermometer for each system. Choose heating or cooling and then set the desired temperature Overview Sub-menus Set the temperature (with room sensors installed and INDOOR CLIMATE activated): temperature heating...
  • Page 16 RC-HY20/40-W – at your service Menu 1.3 - temperature scheduling degree change of the indoor temperature depends on the scheduled for each weekday. You can also schedule a longer period during a selected period in the display. scheduling 1.3 CAUTION An increase in the room temperature can be slowed by the thermostats for the radiators or under floor heating.
  • Page 17 RC-HY20/40-W – at your service Time period: The start and stop time for the selected day for Time period: The start and stop time for the selected day for scheduling are selected here. scheduling are selected here. Adjusting: Adjusting: relation to menu 1.1 during scheduling is set here. If the rooms permitted.
  • Page 18 RC-HY20/40-W – at your service Menu 1.9 - advanced advanced 1.9 curve external adjustment water to the heating system, supply temperature, and therefore min. flow line temp. room sensor settings how the supply temperature changes at different outdoor cooling settings temperatures here.
  • Page 19 RC-HY20/40-W – at your service Flow line temperature – maximum and minimum values Wait 24 hours before making a new setting, so that the room temperature has time to stabilise. If it is cold outdoors and the room temperature is too low, increase the curve slope by one increment.
  • Page 20 RC-HY20/40-W – at your service Menu 1.9.3 - min. flow line temp. Menu 1.9.4 - room sensor settings factor system min. flow line temp. heating 1.9.3.1 room sensor settings 1.9.4 climate system 1 °C control room sensor syst 1 climate system 2 °C heating factor system climate system 3...
  • Page 21 RC-HY20/40-W – at your service Menu 1.9.5 - cooling settings time betw. switch heat/cool cooling 1.9.5 delta at +20 °C °C delta at +40 °C °C periods of the year. CAUTION heat/cool sen. BT74 Certain setting options only appear if their function is set pt value cool/heat sensor °C installed and activated in RC-HY20/40-W.
  • Page 22 RC-HY20/40-W – at your service step difference compressors (RC-HY40-W only) CAUTION Curve 0 in menu 1.9. 1 must be selected for own curve to CAUTION apply. This setting option only appears if cooling is activated in menu 5.2.4. Menu 1.9.8 - point offset point offset 1.9.8 compressor is to start is set here.
  • Page 23: Set The Hot Water Capacity

    RC-HY20/40-W – at your service Set the hot water capacity CAUTION Overview If comfort mode "luxury" is selected in menu 2.2 no further increase can be carried out. Sub-menus This menu only appears if a water heater is docked to the heat pump.
  • Page 24 RC-HY20/40-W – at your service Menu 2.3 - scheduling Menu 2.9 - advanced Two different periods of hot water comfort per day can be scheduled here. advanced 2.9 Activated Schedule SCHEDULING HOT WATER periodic increase schedule 1 schedule 2 hot water recirc. activated normal tues...
  • Page 25 RC-HY20/40-W – at your service Menu 2.9.2 - hot water recirc. (accessory required) hot water recirc. 2.9.2 operating time downtime period 1 period 2 period 3 operating time downtime Set the hot water circulation for up to three periods per day here.
  • Page 26: Get Information

    RC-HY20/40-W – at your service Get information Menu 3.1 - service info Information about the actual operating status of the installation Overview changes can be made. Sub-menus scroll between the pages. service info display to the following menus. status AA25 INFO 3 op.
  • Page 27 RC-HY20/40-W – at your service Menu 3.3 - add. heat info Menu 3.5 - indoor temp. log week during the past year. The dotted line indicates the annual be made. If there is more than are climate system the information is on pages.
  • Page 28: Adjust The Heat Pump

    RC-HY20/40-W – at your service Adjust the heat pump Menu 4.1 - plus functions Settings for any additional functions installed in RC- Overview Sub-menus Menu 4.1.1/4.1.2 - Pool 1/Pool 2 temperatures. display to the right of the menus. "plus functions functions in the heating system.
  • Page 29 RC-HY20/40-W – at your service Menu 4.1.3 - internet Disconnect all users internet. NOTE After disconnecting all users, none of them can monitor or control your installation via myUplink without requesting a new connection code Menu 4.1.3.8 - tcp/ip settings Automatic setting (DHCP) NOTE settings using DHCP.
  • Page 30 RC-HY20/40-W – at your service Menu 4.1.3.9 - proxy settings Menu 4.1.5 - SG Ready Internet. These settings are primarily used when the installation and HTTP Digest type. If unsure about applicable settings, contact your network affect room temperature Here you set whether room temperature should be affected Setting affect hot water 5.
  • Page 31 RC-HY20/40-W – at your service Menu 4.1.6 - Smart price adaption™ area Menu 4.1.8 - smart energy source™ (RC-HY40-W In this menu you state where the heat pump is located and how only) great a role the electricity price should play. The greater the SMART ENERGY SOURCE 4.1.8 increased risk of affecting comfort.
  • Page 32 RC-HY20/40-W – at your service Menu 4.1.8.1 - settings set. price 4.1.8.2 settings 4.1.8.1 price, extern step add. tariff price per kWh, low tariff smart energy source price per kWh, high tariff control method price per kWh tariff set. price 4.1.8.2 price per kWh, low tariff settings 4.1.8.1 price per kWh, high tariff...
  • Page 33 RC-HY20/40-W – at your service Menu 4.1.8.3 - CO2 impact Menu 4.1.8.6 - tariff per, ext. shunt add CO2 impact 4.1.8.3 additional heat. CO2, electricity CO2, ext. shunted contr. add. CO2, ext. step contr. add. tariff per, ext. shunt add 4.1.8.6 date date...
  • Page 34 RC-HY20/40-W – at your service affect hot water CAUTION You cannot change from only additional heat if you do not have a heat pump connected. affect pool temperature Functions "compressor" is that which produces heating and hot water for the accommodation. If "compressor" is deselected, a Menu 4.2 - op.
  • Page 35 RC-HY20/40-W – at your service Menu 4.7 - holiday setting Menu 4.9.1 - op. prioritisation To reduce energy consumption during a holiday you can schedule a reduction in heating and hot water temperature. Cooling can also be scheduled if the functions are connected. applies to all climate systems with room sensors.
  • Page 36 RC-HY20/40-W – at your service the heat pump has the integrated cooling function and it is Menu 4.9.4 - factory setting user for cooling. factory setting user 4.9.4 outdoor temperature is used. Do you want to reset all user settings to factory settings? CAUTION It cannot be set "stop additional heat"...
  • Page 37 RC-HY20/40-W – at your service If you wish to set similar scheduling for every day of the If you wish to set similar scheduling for every day of the week start by filling in “all” and then changing the desired week start by filling in “all”...
  • Page 38: Disturbances In Comfort

    Disturbances in comfort Disturbances in comfort NOTE Always give the product's serial number (14 digits) when In most cases, the controller notes a malfunction and indicates reporting a fault. this with alarms and shows instructions to rectify it in the alarms.
  • Page 39: Additional Heating Only

    Disturbances in comfort Additional heating only   E nter menu 4.9.1 and increase the time for when heating If you are unsuccessful in rectifying the fault and are unable to is to be prioritised. heat the house, you can, whilst waiting for assistance, continue running the heat pump in "add.
  • Page 40: Maintenance

    Maintenance Measurement of the Protective Magnesium Anode Maintenance Wear PT300/500 In order to check the degree of wear of the anode, do the Periodic inspections and maintenance are the conditions of life of the product. 2.   storage tank top head. 3.
  • Page 41 Maintenance Replacement of the Protective Magnesium Anode Cleaning of the Storage Tank storage tank operation. The amount of deposited scale depends you can use the titanium anode. Install it in accordance with on the water hardness, the operating temperature and operating the anode installation manual.
  • Page 42 Maintenance Cleaning the outer casing FDCM100/140VNX-W If necessary the outer casing can be cleaned using a damp cloth. maintenance is required. NOTE Insufficient oversight can cause serious damage to FDCM coming into contact with alkaline cleaning agents. and other unit which is not covered by the guarantee. Checking grilles and bottom panel on FDCM anything else regularly throughout the year.
  • Page 43: Checklist

    Checklist Checklist: Checks before commissioning Hot water Notes Checked Heating Notes Checked ______ℓ ℓ Cooling Notes Checked Electrical installation Notes Checked Accessories Notes Checked Yes/No ℓ Yes/No Yes/No ______ Setting (Menu 1.9.4, 1.9.5) EN-41...
  • Page 44: Glossary

    Glossary DUT, dimensioned outdoor temperature Glossary The dimensioned outdoor temperature differs depending on Additional heat The additional heat is the heat produced in addition to the heat Efficiency heating. Calculated flow line temperature Electrical addition The temperature that the heat pump calculates that the heating system requires for an optimum accommodation temperature.
  • Page 45 Glossary Pressostat high pressure pressostat trips if the condensing pressure is too pressure is too low. Radiator Return pipe The line in which the water is transported back to the heat Return temp The temperature of the water that returns to the heat pump after Room sensor how hot it is indoors.
  • Page 46 5 The Square, Stockley Park, Uxbridge, Middlesex, UB11 1ET, United Kingdom Tel : +44-333-207-4072 Fax : +44-333-207-4089 http://www.mhiae.com/ MHIAE SERVICES B.V. (Wholly-owned subsidiary of MITSUBISHI HEAVY INDUSTRIES AIR-CONDITIONING EUROPE, LTD.) Herikerbergweg 238, Luna ArenA, 1101 CM Amsterdam, Netherlands P.O.Box 23393 1100 DW Amsterdam, Netherlands Tel : +31-20-406-4535 http://www.mhiaeservices.com/...

Table of Contents