Calculating The Heat Demand For Dhw Heating For Sports Halls; Calculating The Heat Demand For Dhw Heating In Connection With District Heating Systems - Viessmann Vitocell 100-H Technical Manual

Hide thumbs Also See for Vitocell 100-H:
Table of Contents

Advertisement

Sizing
(cont.)
As the showering process repeats hourly, the selected cylinder
capacity must be heated up within 1 hour. The heat volume required
to achieve this is calculated as follows:
V
· ΔT
· c
cyl.
A
= Φ
=
²
A
A
Z
A
600 · 1 · (60 – 10)
=
860 · 1
= 34.9 kW
or Φ
= Minimum connected load for heating the DHW cylinder in
²
A
A
kW
V
=
Capacity in litres
cyl

Calculating the heat demand for DHW heating for sports halls

Observe DIN 18032-1, April 1989 "Sports grounds, sports halls" as a
guideline for the sizing, design and installation of the DHW system.
DHW is drawn-off in sports halls in short bursts.
Therefore, when it comes to selecting suitable DHW cylinders, the
main criterion is the "Peak draw-off rate" (10-minute peak output).
The DHW heating system must be capable of ensuring the DHW deliv-
ery over the entire period of use (throughout the year).
The following values are assumed for sizing the DHW heating
system:
DHW draw-off temperature:
DHW consumption per person µ:
Shower duration per person t:
Heat-up time Z
:
A
People per heat-up time and training unit
n:
Cylinder storage temperature T
a
Example for a simple sports hall:
1. Calculating the required DHW volume:
m
= t · µ · n
MW
= 4 min/person · 8 l/min · 25 persons
= 800 l DHW volume at 40 ºC
Selected capacity: 700 l
(the selected capacity should roughly correspond to the required DHW
volume).
Peak output from the corresponding tables in the datasheets for the
relevant DHW cylinders.
Conversion to DHW outlet temperature of 40 ºC at
m
= Peak output at a DHW outlet temperature of 40 ºC
(40 ºC)
m
= Peak output at a DHW outlet temperature of 45 ºC
(45 ºC)
(according to table in DHW cylinder datasheet)
45 – 10
m
= m
·
(40°C)
(45°C)
40 – 10
= 2 · 424 l/10 min
35
= 848 ·
30
= 989 l/10 min

Calculating the heat demand for DHW heating in connection with district heating systems

DHW heating systems heated by district heating systems instead of
boilers cannot be sized according to the values contained in the DHW
cylinder tables because of different heating water flow and return tem-
peratures in winter and summer.
The following example gives one sizing option.
DHW heating
max. 40 ºC
8 l/min
4 min
50 min
min. 25 people
:
60 ºC
ΔT
=
Temperature differential between the cylinder storage
A
temperature and the cold water inlet temperature
c =
Spec. thermal capacity
1 kWh
860 l · K
Z
=
Heat-up time in h
A
To guarantee adequate heating of the building during winter too, this
heat volume must be added to the heat load. EnEV [Germany] permits
this supplement for the following reasons:
1. This is commercial utilisation.
2. There is no output limit when using a low temperature boiler.
Selected DHW cylinders:
2 × Vitocell 300-H, each with 350 l,
peak output at 70 °ºC heating water flow temperature = 989 l at
40 ºC
2. Calculating the required heat-up output for the calculated cyl-
inder capacity:
V · c · (T
– T
)
a
e
= Φ
=
²
A
A
Z
A
700 · (60 – 10)
=
= 49 kW
860 · 0.833
or Φ
= Heat-up output in kW
²
A
A
V
= Cylinder capacity in l
c
= Spec. thermal capacity
1 kWh
860 l · K
T
= Cylinder storage temperature in ºC
a
T
= Cold water inlet temperature in ºC
e
Size the boiler and circulation pump for cylinder heating according to
the required heat-up output.
To guarantee adequate heating of the building during winter too, this
heat volume must be added to the heat load. EnEV [Germany] permits
this supplement for the following reasons:
1. This is commercial utilisation.
2. There is no output limit when using a low temperature boiler.
4