Below is a list of the parameter description, type and address of data on DMC20 :
Data
Description
DewPoint
DewPoint temperature - T1 probe
Temperature of the incoming air - T2 probe
Air →O
Temperature of the outgoing air - T3 probe
Air ←O
Compr.LP
Suction temperature of the compressor (low pressure side) - T4 probe
Compr.HP
Outlet temperature of the compressor (high pressure side) - T5 probe
Condens.
Condensing temperature - T6 probe
Inlet temperature of the cooling water (Water-Cooled) - T8 probe
Water →O
Ambient
Ambient temperature - T7 probe
1)
Language
Selection of the language for dialogue and alarm messages
DewPoint Set
Not Used
Diff. DewPoint
Not Used
E Drain Time
Not Used
E Drain Pause
Not Used
S Drain Time
Discharge time of the condensate separator
S Drain Pause
Pause between two condensate separator discharges
Display Contrast.
Adjustment of the Display contrast
Min DewPoint
Not Used
Max DewPoint
Not Used
Low DewPoint
Temperature of interv. for the too low DewPoint alarm
Low DP Diff.!
Differential temperature for the too low DewPoint alarm
Low DP Delay!
Delay time for the too low DewPoint alarm
High DewPoint !
Temperature of interv. for the too high DewPoint alarm
High DP Diff.!
Differential temperature for the too high DewPoint alarm
High DP Delay!
Delay time for the too high DewPoint alarm
Condensation !
Temperature of intervention for the too high DewPoint alarm
Condens.Diff.!
Differential temperature for the too high DewPoint alarm
Condens.Delay!
Delay time for the too high DewPoint alarm
Peripheral No
Unit address for serial communication
Working
Operating time of the dryer in hours
Alarm STOP
Presence of an alarm that has stopped the dryer
Alarm Status
Presence of an alarm
Cond. Fan Switch
Status of the condenser fan control pressure switch
Remote ON/OFF
Status of the Remote ON/OFF switch
Switch
DewPoint LOW
Low DewPoint alarm ON
DewPoint HIGH
High DewPoint alarm ON
Condens. HIGH
High Condensation temperature alarm ON
STOP Compr.LP
Cooler low pressure switch (P
STOP Compr.HP
Cooler high pressure switch (P
Protection Fan.
Fan thermal/electrical protections alarm ON (Air-Cooled)
Protection Comp.
Compressor thermal/electrical protections alarm ON
Probe Fault
Probe faulty alarm ON
Stop ! Low DP
STOP enabled in case the DewPoint of the dryer is too low
Stop ! High DP
STOP enabled in case the DewPoint of the dryer is too high
Automatic
Machine enabled to restore its operation after a power black out
Start-up
Recovery After !
Automatic alarms reset
Autom.
ON/OFF DMC20
Status of DMC20 - ON or OFF (Stand-by)
1)
NOTE :
Language selection : 00=Italian - 01=English - 02=German - 03=French
R=Read - W=Write
info@finicompressors.it
) alarm ON
B
) alarm ON
A
- EN -
Type
Register
Address
Signed Integer
0000 - R
Signed Integer
0001 - R
Signed Integer
0002 - R
Signed Integer
0003 - R
Signed Integer
0004 - R
Signed Integer
0005 - R
Signed Integer
0006 - R
Signed Integer
0007 - R
Signed Integer
0200 - R/W
Signed Integer
0201 - R/W
Signed Integer
0202 - R/W
Signed Integer
0203 - R/W
Signed Integer
0204 - R/W
Signed Integer
0205 - R/W
Signed Integer
0206 - R/W
Signed Integer
0207 - R/W
Signed Integer
0208 - R/W
Signed Integer
0209 - R/W
Signed Integer
0210 - R/W
Signed Integer
0211 - R/W
Signed Integer
0212 - R/W
Signed Integer
0213 - R/W
Signed Integer
0214 - R/W
Signed Integer
0215 - R/W
Signed Integer
0216 - R/W
Signed Integer
0217 - R/W
Signed Integer
0218 - R/W
Signed Integer
0219 - R/W
Signed Integer
0246 - R/W
bit - 1=Yes
0100.0 - R
bit - 1=Yes
0100.1 - R
bit - 1=ON
0101.3 - R
bit - 0=Local
0101.6 - R
1=Remote
bit - 1=Yes
0102.0 - R
bit - 1=Yes
0102.1 - R
bit - 1=Yes
0102.2 - R
bit - 1=Yes
0102.4 - R
bit - 1=Yes
0102.5 - R
bit - 1=Yes
0102.6 - R
bit - 1=Yes
0102.7 - R
bit - 1=Yes
0102.8 - R
bit - 1=Yes
0220.0 - R/W
bit - 1=Yes
0220.1 - R/W
bit - 1=Yes
0220.2 - R/W
bit - 1=Yes
0220.3 - R/W
bit-1=Stand-by
0220.15 - R/W