Remote Command - Fini RD 185-810 User Manual

Refrigerated
Table of Contents

Advertisement

40069 Zola Predosa (BO) - ITALY
SET-UP PARAMETERS TABLE
Parameter
Pass Code ?
Language
DewPoint Set
L
E
DewPoint Diff. Not Used
V
E
E Drain Time
L
E Drain Pause Not Used
1
S Drain Time
S Drain Pause Pause between two condensate separator discharges
Display Contrast. Adjustment of the Display contrast
Min DewPoint
Max DewPoint Not Used
Low ! DewPoint Temperature of interv. for the too low DewPoint alarm
L
E
Low DP ! Diff.
V
E
Low DP ! Delay Delay time for the too low DewPoint alarm
L
Low DP ! Stop STOP enabled in case the DewPoint of the dryer is too low
2
High DewPoint ! Temperature of interv. for the too high DewPoint alarm
High DP ! Diff. Differential temperature for the too high DewPoint alarm
High DP ! Delay Delay time for the too high DewPoint alarm
High DP ! Stop STOP enabled in case the DewPoint of the dryer is too high
Condensation ! Temp. of intervention for the too high condensation
Condens ! Diff. Differential
Condens. ! Delay Delay time for the too high condensation temp. alarm
Start at
Power Up
Recovery After ! Automatic alarms reset
Peripheral No. Unit address for serial communication

5.17.4 REMOTE COMMAND

It is possible to remotely switch the dryer ON and OFF by means of a simple switch connected with two
wires to the DMC20 (see terminal 20 and 21 on the electric diagram). Closing the contact of the command
switch, on the display appears the message "Stand-by Remote", and no functions will be selectable on the
local panel; as soon as the contact is opened, the dryer returns to the previous condition (Stand-by if it was
in Stand-by condition, ON if it was ON).
I
F INSTALLED
USER WILL BE RESPONSIBLE FOR THE INSTALLATION OF PROPER PROTECTIONS FOR POSSIBLE SUDDEN
POWER RESTORATION TO THE DRYER
Description
Password to access level 2
Selection of the language for dialogue and alarm messages
Not Used
Not Used
Discharge time of the condensate separator
Not Used
Differential temperature for the too low DewPoint alarm
temperature alarm
temp.
temperature alarm
Machine enabled to restore its operation after a power
black out
,
THE REMOTE CONTROL HAS PRIORITY ON THE FRONTAL COMMANDS OF THE
info@finicompressors.it
for
the
too
high
.
Adjustment
Range
0 - 255
Italian - English
German - French
N.A.
N.A.
0 - 50 sec
0.5 - 10 min
0 - 50 sec
0.5 - 10 min
0 - 100
N.A.
N.A.
-10.0 - 0.0 ºC
1.0 - 10.0 ºK
0.5 - 20 min
YES/NO
10.0 - 20.0 ºC
-1.0 - -10.0 ºK
0.5 - 30 min
YES/NO
50.0 - 70.0 ºC
condensation
-1.0 - -10.0 ºK
0.5 - 20 min
YES/NO
YES/NO
01 - 255
- EN -
Std
Value
0
-5 ºC
0.2 ºK
3 sec
4.0 min
4 sec
1.0 min
50
-10 ºC
0 ºC
-5 ºC
6 ºK
10 min
NO
15 ºC
-5 ºK
20 min
NO
60.0 ºC
-5 ºK
10 min
NO
NO
01
DMC20.
THE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents