Termination Clearances; General Information Assembling Vent Pipes; Flex Vent Pipes - Vermont Castings 36CFDVNV Installation And Operating Instructions Manual

Direct vent gas fireplace
Table of Contents

Advertisement

36CFDV Series Gas Fireplace

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.
Inside Corner
G
V
Balcony -
with no side wall
V
M =
Combustible &
Noncombustible
12" (305 mm)
*NOTE: Termination in an alcove space (spaces open only on one side
and with an overhang) is permitted with the dimensions specified for
vinyl or non-vinyl siding and soffits. 1. There must be a 3' (914 mm) mini-
Figure 15 -
Termination Clearances

GENERAL INFORMATION ASSEMBLING VENT PIPES

USA Installations
The venting system must conform to local codes and/or
the current National Fuel Code ANSI Z223.1/NFPA 54.
Only venting components manufactured or approved by
Vermont Castings Group may be used in Direct Vent sys-
tems.
Canadian Installations
The venting system must be installed in accordance with
the current CSA-B149.1 installation code.

FLEX VENT PIPES

Secure flex vent pipe in place with a hose clamp (pro-
vided).
*Be sure the flex pipe overlaps at least 1" (25 mm) onto
the collars of the fireplace and termination. If the termina-
tion has an internal bead, be sure to overlap and secure
1" (25 mm) past the bead.
14
Outside Corner
G =
Combustible
6" (152 mm)
V
Noncombustible
2" (51 mm)
Balcony -
with perpendicular side wall
M
Combustible &
Noncombustible
M = 12" (305 mm)
P = 6" (152 mm)
VENTING INSTALLATION INFORMATION
F =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
F
M
V
P
mum between termination caps. 2. All mechanical air intakes within 10'
(1 m) of a termination cap must be a minimum of 3' (914 mm) below the
termination cap. 3. All gravity air intakes within 3' (914 mm) of a termina-
tion cap must be a minimum of 1' (305 mm) below the termination cap.
* Be sure the vent is actually crushed before proceeding.
Apply a tug to be sure the vent will not slip off the collars.
Repeat process with 7" flex vent pipe. The same proce-
dure must be performed on the vent side.
FP2290
Figure 16 -
Suecure Flex Vent Pipe with Hose Clamps.
Alcove Applications*
D
C
V
O
E
= Min. 2" (51 mm) for
non-vinyl sidewalls
Min. 12" (305 mm) for
vinyl sidewalls
O
= 8' (2.4 m) Min.
No.
of Caps
D
Min.
1
3' (914 mm) 2 x D
2
6' (1.8 m)
3
9' (2.7 m)
4
12' (3.7 m)
D
= # of Termination caps x 3
Min.
C
= (2 / # termination caps) x D
Max.
C
E
C
Max.
Actual
1 x D
Actual
2/3 x D
Actual
1/2 x D
Actual
Actual
584-15
Hose Clamp
20305832