Thick Facing with Fireplace Xtrordinair (FPX) Arched Faces

The following illustration shows facing considerations for those fireplaces utilizing FPX arched faces.
The facing must be non-combustible and over 1" (25mm) in depth.
The Fireplace Xtrordinair 564
Masonry Template is
recommended for masonry
installation (sku 98500674). The
template helps locate and
support the masonry as it being
installed.
Before installing masonry, install
the FPX Face Upgrade Kit
(98500683). This covers the
upper corners.
TOP VIEW
Fireplace
Face
Masonry
© Travis Industries
Installation
Framing
Nailing Bracket
Drywall
(for qualified installers only)
Masonry Line
Floor-Mounted Fireplaces or Raised Hearths:
Build the hearth 1" max (25mm) above the base
of the fireplace. The fireplace may be raised to
accommodate thicker hearth materials.
Raised Fireplaces:
Masonry is installed 1" maximum
(25mm) above the base of the
fireplace.
FRONT VIEW
61" Radius (1549mm)
36-1/4"
921mm
4140926
2-3/4"
70mm
29"
737mm
1"
25mm
100-01395