D. Chimney Termination Requirements
Follow manufacturer's instructions for clearance, securing
fl ashing and terminating the chimney.
Must have an approved and listed cap
Must not be located where it will become plugged by
snow or other material
Must terminate at least 3 feet (91cm) above the roof
and at least 2 feet (61cm) above any portion of the
roof within 10 feet (305cm).
Must be located away from trees or other struc-
tures
E. 2-10-3 Rule
These are safety requirements and are not meant to assure proper fl ue draft.
3 ft. (91cm)
Minimum
Figure 17.1
Wall or Parapet
Figure 17.2
October 13, 2015
2 ft. (61cm)
10 ft. (305cm) To Nearest Roofline
10 ft. (305cm) or more
3 ft. (91cm) Minimum
2100 Millennium Wood Stove (ACC)
NOTE:
Chimney performance may vary.
Trees, buildings, roof lines and wind conditions affect
performance.
Chimney height may need adjustment if smoking or
overdraft occurs.
Less than 10 ft. (305cm)
Pitched Roof
3 ft. (91cm) Minimum
Flat Roof
7039-131M
2 ft. (61cm)
3 ft. (91cm)
Minimum
Less than 10 ft. (305cm)
2 ft. (61cm) Minimum