D. Chimney Termination Requirements
Follow manufacturer's instructions for clearance, securing
fl ashing and terminating the chimney.
•
Must have an approved and listed cap
•
Must not be located where it will become plugged by
snow or other material
•
Must terminate at least 3 feet (91cm) above the roof
and at least 2 feet (61cm) above any portion of the
roof within 10 feet (305cm).
•
Must be located away from trees or other struc-
tures
E. 2-10-3 Rule
These are safety requirements and are not meant to assure proper fl ue draft.
3 ft. (91cm)
Minimum
Figure 17.1
Wall or Parapet
Figure 17.2
October 13, 2015
2 ft. (61cm)
10 ft. (305cm) To Nearest Roofline
10 ft. (305cm) or more
3 ft. (91cm) Minimum
2100 Millennium Wood Stove (ACC)
NOTE:
•
Chimney performance may vary.
•
Trees, buildings, roof lines and wind conditions affect
performance.
•
Chimney height may need adjustment if smoking or
overdraft occurs.
Less than 10 ft. (305cm)
Pitched Roof
3 ft. (91cm) Minimum
Flat Roof
7039-131M
2 ft. (61cm)
3 ft. (91cm)
Minimum
Less than 10 ft. (305cm)
2 ft. (61cm) Minimum
Page 17