when (H
) < (V
)
T
T
See graph to determine the required vertical rise V
required horizontal run H
.
T
REQUIRED VERTICAL
RISE IN FEET
V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET
The shaded area within the lines represents acceptable
values for H
and V
.
T
T
For vent confi gurations requiring more than zero 90° elbow
(top exit) or one 90° elbow (rear exit), the following formulas
apply:
Formula 1: H
< V
T
T
Formula 2: H
+ V
T
T

VERTICAL TERMINATION

FIGURE 10
for the
T
< 40 feet
Example 4:
FIGURE 11
V
1
V
= 5 ft
1
V
= 6 ft
2
V
= 10 ft
3
V
= V
+ V
+ V
T
1
2
H
= 8 ft
1
H
= 2.5 ft
2
H
= H
+ H
= 8 + 2.5 = 10.5 ft
R
1
2
H
H
= .03 (four 90° elbows - 90°)
O
T
= .03 (90 + 90 + 90 + 90 - 90) = 8.1 ft
H
= H
+ H
T
R
O
H
+ V
= 18.6 + 21 = 39.6 ft
T
T
Formula 1:
H
< V
T
18.6 < 21
Formula 2:
H
+ V
T
39.6 < 40
Since both formulas are met, this vent confi guration is
acceptable.
90°
90°
H
V
2
2
H
1
90°
= 5 + 6 + 10 = 21 ft
3
= 10.5 + 8.1 = 18.6 ft
T
< 40 feet
T
W415-0666 / 01.28.08
9
V
3
90°