Existing Installations; Condensate Disposal; Circulating Air Requirements; Plenums & Air Ducts - Nordyne TC Series User Manual

Two-stage condensing gas furnaces with fixed & variable speed blowers
Table of Contents

Advertisement

Maximum Flue Pipe Length (FEET)
Winter Design
in Unconditioned & Exterior Spaces
Temperature
Without Insulation
20
0
-20
*NOTE: Insulation thickness greater than 3/8 inch, based on an
R value of 3.5 (ft x F x hr) / (BTU x in.)
Table 2. Vent Protection

Existing Installations

When an existing furnace is removed from a vent system
serving other appliances, the existing vent system may
not be sized properly to vent the remaining appliances
(For example: water heater). An improperly sized venting
system can result in the formation of condensate, leakage,
or spillage. The existing vent system should be checked
to make sure it is in compliance with NFGC and must be
brought into compliance before installing the furnace.
NOTE: If replacing an existing furnace, it is possible you
will encounter an existing plastic venting system that is
subject to a Consumer Product Safety Commission recall.
The pipes involved in the recall are High Temperature
Plastic Vent (HTPV). If your venting system contains
these pipes DO NOT reuse this venting system! This
recall does not apply to other plastic vent pipes, such
as white PVC or CPVC. Check for details on the CPSC
website or call their toll-free number (800) 758-3688.

Condensate Disposal

The method for disposing of condensate varies according
to local codes. Consult your local code or authority having
jurisdiction.
Each of the condensate drain lines must be J-trapped
using field supplied parts. After the condensate lines are
J-trapped, they may be combined together into a single
run to the drain. The drain lines must be routed downward
to ensure proper drainage from furnace.
Neutralizer kit P/N 902377 is available for use with this
furnace. Please follow the instructions provided with
the kit.
For Installations where there is limited clearance for the
J-Trap (such as an attic where it may be installed between
ceiling joists), either side of the J-Trap can be shortened
to a minimum of 3 Inches. See
14
With Insulation*
45
70
20
70
10
60
Figure 11, (page
16).

CIRCULATING AIR REQUIREMENTS

WARNING:
Do not allow combustion products to enter the
circulating air supply. Failure to prevent the
circulation of combustion products into the
living space can create potentially hazardous
conditions including carbon monoxide
poisoning that could result in personal injury
or death.
All return ductwork must be secured to
the furnace with sheet metal screws. For
installations in confined spaces, all return
ductwork must be adequately sealed. When
return air is provided through the bottom of the
furnace, the joint between the furnace and the
return air plenum must be air tight.
The surface that the furnace is mounted on must
provide sound physical support of the furnace
with no gaps, cracks or sagging between the
furnace and the floor or platform.
Return air and circulating air ductwork must
not be connected to any other heat producing
device such as a fireplace insert, stove, etc.This
may result in fire, explosion, carbon monoxide
poisoning, personal injury, or property damage.
Plenums & Air Ducts
• Plenums and air ducts must be installed in accordance
with the Standard for the Installation of Air Conditioning
and Ventilating Systems (NFPA No. 90A) or the
Standard for the Installation of Warm Air Heating and
Air Conditioning Systems (NFPA No. 90B).
Table 6 (page
33),
Table 7 (page
8 (page 35)
contain the maximum airflow and
temperature rise data for fixed and variable speed
motors. If the maximum airflow is 1,600 CFM or more,
it is recommended that two openings be used for return
air on upflow furnaces. Downflow furnaces can only use
one return opening.
• It is recommended that the outlet duct contain a
removable access panel. The opening should be
accessible when the furnace is installed in service and
shall be of a size that smoke or reflected light may be
observed inside the casing to indicate the presence of
leaks in the heat exchanger. The cover for the opening
shall be attached in such a way as to prevent leaks.
• If outside air is used as return air to the furnace for
ventilation or to improve indoor air quality, the system
must be designed so that the return air is not less than
34), &
Table

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tl series

Table of Contents