Toshiba RAV-SM562BT-E Service Manual/Integration page 96

Air conditioner split type
Hide thumbs Also See for RAV-SM562BT-E:
Table of Contents

Advertisement

[P03 error]
Is protective control such as
discharge temprelease control normal?
YES
Is charged refrigerant amount normal?
YES
Is not abnormal overload?
NO
Are characteristics of
TD sensor resistance value normal?
YES
[H01 error]
Is power voltage normal?
YES
Is not abnormal overload?
NO
Is the circuit detected by
current sensor normal?
YES
NO
Are connections of
cable/connector normal?
YES
NO
YES
NO
* Refer to Characteristics-4.
NO
YES
NO
– 96 –
NO
Correct the cabling and
connection of connector.
Check parts. Defect
Check and correct the charged
refrigerant amount.
Improve and delete the cause
Replace TD sensor.
Check CDB.
Defect
* For RAV-SM562AT-E, replace control P.C. board.
Improve power line.
Improve and delete the cause.
Check and correct circuit cables.
Check IPDU.
Defect
* For RAV-SM562AT-E, replace control P.C. board.
®
Replace
®
Replace
®
Replace