Toshiba RAV-SM562BT-E Service Manual/Integration page 93

Air conditioner split type
Hide thumbs Also See for RAV-SM562BT-E:
Table of Contents

Advertisement

[P29 error]
Are connections of
cable/connector normal?
YES
Is compressor normal?
YES
[H03 error]
Are cablings of power and
current sensor normal?
YES
Check IPDU.
®
Defect
Replace
NO
NO
Is not earthed?
NO
Is not winding shorted?
(Is resistance between windings 0.6 to 1.2
NO
Is not winding opened?
NO
Check IPDU P.C. board.
®
Defect
Replace
NO
* For RAV-SM562AT-E, replace control P.C. board.
YES
YES
W
?)
YES
* For RAV-SM562AT-E, replace control P.C. board.
– 93 –
Check and correct circuit cabling
such as cabling to compressor.
®
Compressor error
Replace
®
Compressor error
Replace
®
Compressor error
Replace
Check and correct circuit cables.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents