<Super Digital Inverter>
Model name
Power supply
Type
Compressor
Motor
Pole
Refrigerant charged
Refrigerant control
Standard length
Min. length
Max. total length
Inter connecting
pipe
Additional refrigerant charge under
long piping connector
Height
difference
Height
Outer
Width
dimension
Depth
Appearance
Total weight
Heat exchanger
Fan
Fan unit
Standard air flow
Motor
Gas side
Connecting pipe
Liquid side
Sound pressure level
Cooling/Heating
Sound power level
Cooling/Heating
Outside air temperature, Cooling
Outside air temperature, Heating
RAV-
1 phase 230V (220 – 240V) 50Hz (Power exclusive to outdoor is required.)
(kW)
(kg)
(m)
(m)
(m)
(21m to 50m)
Outdoor lower
(m)
Outdoor higher
(m)
(mm)
(mm)
(mm)
(kg)
(m³/h)
(W)
(mm)
(mm)
(dB•A)
(dB•A)
(°C)
(°C)
SP562AT-E
SP802AT-E
Hermetic compressor
2.0
2.0
4
4
1.5
2.1
Pulse motor valve
7.5
7.5
5.0
5.0
50
50
20g/m
40g/m
(31m to 50m)
30
30
30
30
795
795
900
900
320
320
Silky shade (Muncel 1Y8.5/0.5)
55
62
57
57
63
63
12.7
15.9
6.4
9.5
46/47
47/49
63/64
64/66
– 18 –
SP1102AT-E
3.75
4
2.95
7.5
5.0
70
40g/m
(31m to 70m)
30
30
1340
900
320
95
Finned tube
Propeller fan
125
63 + 63
15.9
9.5
49/51
66/68
43 to –15
15 to –15
SP1402AT-E
3.75
4
2.95
7.5
5.0
70
40g/m
(31m to 70m)
30
30
1340
900
320
95
125
63 + 63
15.9
9.5
53/54
70/71