Toshiba RAV-SM562BT-E Service Manual/Integration page 32

Air conditioner split type
Hide thumbs Also See for RAV-SM562BT-E:
Table of Contents

Advertisement

RAV-SM802UT-E, RAV-SM802BT-E, RAV-SM802CT-E / RAV-SM802AT-E
Outer diameter of refrigerant pipe
Gas side ØA
15.9mm
TS
TD
sensor
sensor
Accumulator
(1000cc)
Rotary
compressor
(DA150A1F-20F)
Pressure
(MPa)
Pd
Ps
Standard 3.28 0.86 33.4
Cooling
Overload 3.59 1.00 33.6 10.2
Low load 1.85 0.83 18.9
Standard 2.53 0.62 25.8
Heating
Overload 3.42 1.07 34.9 10.9
Low load 1.99 0.23 20.3
4 poles are provided to this compressor.
*
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
Liquid side ØB
9.5mm
Pd
2-step
muffler
Ø25 × 200L
4-way valve
(STF-0213Z)
Pipe surface temperature (°C)
(kg/cm²G)
Discharge
Suction
Pd
Ps
(TD)
(TS)
8.8
84
11
82
17
8.5
42
8
6.3
75
3
80
20
2.3
89
–19
Indoor unit
Air heat exchanger
TC sensor
Refrigerant pipe
at gas side
Ø15.9
Packet valve
Packed valve
Outer dia. ØA
Outdoor unit
TO sensor
TE
sensor
Heat exchanger
Ø8 ripple, 2 rows,
20 steps
FP1.3 flat fin
Indoor heat
Outdoor heat
exchanger
exchanger
(TC)
(TE)
10
45
16
51
6
23
42
2
54
17
34
–18
– 32 –
TCJ
sensor
Refrigerant pipe
at liquid side
Ø9.5
Packet valve
Packed valve
Outer dia. ØB
PMV
(Pulse Motor Valve)
(CAM-B30YGTF-1)
Strainer
Distributor
R410A 1.6 kg
Indoor/Outdoor
Compressor
temp. conditions
revolutions per
Indoor
(DB/WB) (°C)
second (rps)
fan
Indoor
83
HIGH
27/19
76
HIGH
32/24
35
LOW
18/15.5
95
HIGH
20/–
50
LOW
28/–
120
HIGH
15/–
Min.
Max.
5m
30m
Ps
Cooling
Heating
Outdoor
35/–
43/–
–5/–
7/6
24/18
–10/(70%)