Outer diameter of refrigerant pipe
Gas side ØA
Liquid side ØB
15.9mm
9.5mm
TD sensor
Accumulator
Rotary
(2500cc)
compressor
(DA220A2F – 20L)
Pressure
(MPa)
Pd
Ps
Standard 3.44 0.92 35.1
Cooling
Overload 3.73 1.18 38.1 12.0
Low load 1.49 0.70 15.2
Standard 2.80 0.61 28.6
Heating
Overload 3.43 1.08 35.0 11.0
Low load 2.20 0.25 22.4
4 poles are provided to this compressor.
*
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
Refrigerant pipe
at gas side
Ø15.9
Packet valve
Ball valve
Outer dia. ØA
Strainer
TS sensor
4-way valve
(STF-0213Z)
Heat exchanger
Muffler
Outer side
Ø8, 2 rows, 20 steps
Ø25 × L210
FP1.3 flat fin
Inner side
Ø25 × L180
Ø9.52 row, 30 steps
FP1.5 flat fin
Pipe surface temperature (°C)
(kg/cm²G)
Discharge
Suction
Pd
Ps
(TD)
(TS)
9.4
82
8
82
15
7.1
39
8
6.2
80
0
82
14
2.6
76
–19
Indoor unit
TCJ sensor
Strainer
Air heat exchanger
Outdoor unit
TO sensor
TE
sensor
Indoor heat
Outdoor heat
exchanger
exchanger
(TC)
(TE)
10
39
17
48
3
22
46
1
55
13
36
–16
– 33 –
Distributor
(Strainer incorporated)
TC sensor
Refrigerant pipe
at liquid side
Ø9.5
Packet valve
Packed valve
Outer dia. ØB
PMV
(Pulse Motor Valve)
(UKV-25D22)
Distributor
R410A 2.5kg
Indoor/Outdoor
Compressor
temp. conditions
revolutions per
Indoor
(DB/WB) (°C)
second (rps)
fan
Indoor
47
HIGH
27/19
42
HIGH
32/24
30
LOW
18/15.5
48
HIGH
20/–
24
LOW
30/–
55
HIGH
15/–
Min.
Max.
5m
50m
Strainer
Cooling
Heating
Outdoor
35/–
43/–
–5/–
7/6
24/18
–10/(70%)