2.

Accessory Parts

Accessory parts
Part name
Installation plate
Wireless remote controller
Battery
Remote control holder
Mounting screw Ø4 × 25
Pan head wood screw Ø3.1 × 16
<Others>
Name
Owner's manual
Installation manual
Paper pattern
9-EN
Installation Manual
Q'ty
Shape
1
1
2
1
6
2
– 9 –
SMMS High-Wall Type
3.

Selection of Installation Place

WARNING
• Install the air conditioner at enough strong place to withstand the weight of the unit.
If the strength is not enough, the unit may fall down resulting in injury.
CAUTION
• Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas.
If a combustible gas leaks and stays around the unit, a fire may occur.
Upon approval of the customer, install the air conditioner in a place that satisfies the
following conditions.
• Place where the unit can be installed horizontally.
• Place where a sufficient servicing space can be ensured for safety maintenance and check.
• Place where drained water will not cause any problem.
Avoid installing in the following places.
• Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide
gas (hot spring).
(Should the unit be used in these places, special protective measures are needed.)
• A restaurant kitchen where a lot of oil is used or place near machines in a factory (Oil adhering to the
heat exchanger and resin part (cross flow fan) in the indoor unit may reduce the performance, generate
mist or dew drop, or deform or damage resin parts.)
• Place where organic solvent is used nearby.
• Place close to a machine generating high frequency.
• Place where the discharged air blows directly into the window of the neighbour house. (Outdoor unit)
• Place where noise of the outdoor unit is easily transmitted.
(When install the outdoor unit on the boundary with the neighbour, pay due attention to the level of noise.)
• Place with poor ventilation.
• Do not use the air conditioner for special purposes such as preserving food, precision instruments, or art
objects, or where breeding animals or growing plants are kept. (This may degrade the quality of
preserved materials.)
• Place where any of high-frequency appliances (including inverter devices, private power generators,
medical equipment, and communication equipment) and inverter-type fluorescent light is installed.
(A malfunction of the air conditioner, abnormal control, or problems due to noise to such appliances /
equipment may occur.)
• When the wireless remote controller is used in a room equipped with an inverter-type fluorescent light or
at a place exposed to direct sunlight, signals from the remote controller may not be received correctly.
• Place where organic solvent is used.
• Place near a door or window exposed to humid outside air (Dew dropping may form.).
• Place where special spray is used frequently.