Toshiba MMK-AP0074MH-E Service Manual page 59

Hide thumbs Also See for MMK-AP0074MH-E:
Table of Contents

Advertisement

Check code
Wired
Outdoor 7-segment display
remote
Check code
Auxiliary code
controller
F15
F15
F16
F16
F22
F22
F23
F23
F24
F24
F29
F31
F31
H01
H01
01: Compressor 1 side
02: Compressor 2 side
03: Compressor 3 side
H02
H02
01: Compressor 1 side
02: Compressor 2 side
03: Compressor 3 side
H03
H03
01: Compressor 1 side
02: Compressor 2 side
03: Compressor 3 side
(∗1) All stop only in case of the header unit. The follower unit continues operation.
Detected
Check code name
Status
position
I/F
Outdoor temp sensor
All stop
miscabling (TE1, TL)
I/F
Outdoor pressure sensor
All stop
miscabling (Pd, Ps)
TD3 sensor error
I/F
All stop
I/F
Ps sensor error
All stop
I/F
Pd sensor error
All stop
Indoor
Indoor other error
Corresponding
unit only stops.
I/F
Outdoor EEPROM error
All stop
(∗1)
IPDU
Compressor breakdown
All stop
IPDU
Compressor error (lock)
All stop
IPDU
Current detection circuit
All stop
system error
Error detection condition
During operation of compressor in HEAT
• Check installation of TE1 sensor and TL sensor.
mode, the TE1 detection temp was higher
• Check characteristics of TE1 and TL sensor resistance value.
than that of TL by the specified value
• Check outdoor P .C. board (I/F) error.
continued for 3 minutes or more.
High-pressure Pd sensor and low-pressure
• Check connection of high-pressure Pd sensor connector.
Ps sensor were exchanged, or output
• Check connection of low-pressure Ps sensor connector.
voltages of both sensors are zero.
• Check pressure sensors Pd and Ps error.
• Check outdoor P .C. board (I/F) error.
• Check compression error of compressor.
Sensor resistance value is infinite or 0
• Check connection of TD3 sensor connector.
(Open/Short)
• Check resistance value characteristics of TD3.
• Check error of outdoor P .C. board (I/F).
Output voltage of Ps sensor was zero.
• Misconnection of Ps sensor and Pd sensor connectors
• Check connection of Ps sensor connector.
• Check Ps sensor error.
• Check compression error of compressor.
• Check 4-way valve error.
• Check outdoor P .C. board (I/F) error.
• Check SV4 circuit error.
Output voltage of Pd sensor was zero.
• Check connection of Pd sensor connector.
(Sensor Open)
• Check Pd sensor error.
Pd > 4.15MPa during stop of compressor
• Check outdoor P .C. board (I/F) error.
Indoor P .C. board did not operate normally.
• Check indoor P .C. board error (EEPROM error).
Outdoor P .C. board (I/F) did not operate
• Check power voltage.
normally.
• Check power noise.
• Check outdoor P .C. board (I/F) error.
Inverter current detection circuit detected
• Check power voltage. (AC380–415V ± 10%).
over-current and stopped.
• Check compressor error.
• Check cause of abnormal overload operation.
• Check outdoor P .C. board (Comp. IPDU) error.
Over-current was detected several seconds
• Check compressor error.
after header compressor had started.
• Check power voltage. (AC380–415V ±10%).
• Check cable of compressor and phase-missing.
• Check connector/terminal connection on IPDU P .C. board.
• Check conduction of case heater.
(Check activation error due to liquid stagnation in compressor.)
• Check outdoor P .C. board (Comp. IPDU) error.
While header compressor stopped, current
• Check cabling of current detection circuit system.
flowed more than the specified current and
• Check outdoor P .C. board (Comp. IPDU) error.
was detected.