Accessory Parts; Installation Of R32 Refrigerant Air Conditioner - Toshiba RAV-GM1601ATP-E Installation Manual

Hide thumbs Also See for RAV-GM1601ATP-E:
Table of Contents

Advertisement

1

Accessory parts

Part name
Q'ty
Shape
Installation Manual
1
Booklet
Drain nipple
1
Waterproof rubber cap
5
Protective bush
1
Guard material for
1
passage part
Rub-Sheet
1
Safety Manual
1
Usage
Hand this directly to the customer.
For protecting wires (pipe cover)
For protecting passage part (pipe cover)
For protecting small lizard.
For hand over directly to the customer
– 3 –
2
Installation of R32 refrigerant air
conditioner
CAUTION
R32 refrigerant air conditioner installation
This air conditioner adopts the HFC refrigerant (R32) which does not destroy ozone layer.
Therefore, during installation work, make sure that water, dust, former refrigerant, or refrigerant oil does not enter
the R32 refrigerant air conditioner cycle. To prevent mixing of refrigerant or refrigerant oil, the sizes of connecting
sections of charge port on the main unit and installation tools are different from those of the conventional
refrigerant units.
Accordingly, special tools are required for the R32 or R410A refrigerant units. For connecting pipes, use new and
clean piping materials with high pressure fittings made for the R32 or R410A only, so that water and/or dust does
not enter.
When using existing piping, refer to "14 Appendix - [1] Existing piping".
Required Tools/Equipment and Precautions for use
Prepare the tools and equipment listed in the following table before starting the installation work.
Newly prepared tools and equipment must be used exclusively.
Legend
: Conventional tools (R32 or R410A)
: Prepared newly (Use for R32 only)
Tools / equipment
Gauge manifold
Vacuuming / charging refrigerant
and operation check
Charging hose
Charging cylinder
Can not be used
Gas leak detector
Charging refrigerant
Vacuum pump
Vacuum drying
Vacuum pump with backflow
Vacuum drying
prevention function
Flare tool
Flare machining of pipes
Use
How to use tools / equipment
Conventional tools (R410A)
Conventional tools (R410A)
Unusable (Use the electronic refrigerant charging
scale)
Conventional tools (R32 or R410A)
Conventional tools (R32 or R410A)
Usable if the backflow prevention adapter is
installed.
Conventional tools (R32 or R410A)
Conventional tools (R410A)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-gm1601atjp-e

Table of Contents