Toshiba MMK-AP0074MH-E Service Manual page 62

Hide thumbs Also See for MMK-AP0074MH-E:
Table of Contents

Advertisement

Check code
Wired
Outdoor 7-segment display
remote
Check code
Auxiliary code
controller
L05
L06
L06
No. of indoor units with priority
L07
L08
L08
L09
L10
L10
L20
L28
L28
L29
L29
A-3-IPDU
FAN
IPDU
1
2
3
01 ¡
02
¡
03 ¡ ¡
04
¡
05 ¡
¡
06
¡ ¡
07 ¡ ¡ ¡
08
¡
09 ¡
¡
L30
L30
Detected indoor address
L31
Detected
Check code name
position
I/F
Duplicated indoor units with priority
(Displayed on indoor unit with priority)
I/F
Duplicated indoor units with priority
(Displayed on the unit other than
indoor unit with priority)
Indoor
Group line in individual indoor unit.
Indoor
Indoor group / address unset
Indoor
Indoor capacity unset
I/F
Outdoor capacity unset
TCC-Link
Duplicated central control addresses
Indoor
I/F
Quantity over of connected outdoor
units
I/F
IPDU quantity error
A-3-IPDU
FAN
IPDU
1
2
3
0A
¡
¡
0B ¡ ¡
¡
0C
¡
¡
0D ¡
¡
¡
0E
¡ ¡
¡
0F ¡ ¡ ¡
¡
¡ mark:
Error position.
Interlock in indoor unit from outside
Indoor
Extended IC (Integrated Circuit) error
I/F
Status
Error detection condition
All stop
Indoor units with priority were
duplicated.
All stop
Indoor units with priority were
duplicated.
Corresponding
At least one indoor unit
unit only stops.
connected to a group existed in
the individual indoor units.
Corresponding
Address was not yet set up.
unit only stops.
Corresponding
Indoor unit capacity was unset.
unit only stops.
All stop
On the I/F P .C. board for
service, jumper line was not cut
according to the model.
All stop
Duplicated central control
addresses
All stop
There were more than four
outdoor units.
All stop
No. of IPDU units detected
when power was turned on
were less.
Corresponding
• Outside error input terminal
unit only stops.
Detected signal to (CN80) for
more 1 minute
Operation
P .C. board (I/F) parts error
continues.
Check item (position)
• Check display of indoor unit with priority.
• Check display of indoor unit with priority and outdoor
unit.
• Check indoor address.
• Check indoor address.
Note)
After installation, this code is displayed when the power
is firstly turned on.
Set up indoor capacity. (DN=11)
Check model setup on outdoor I/F P .C. board A'ssy for
service.
• Check central control address.
• Check network adaptor P .C. board.
(In case of TCC-Link)
• Check No. of connected outdoor units.
(Max. 4 units per 1 system)
• Check communication line between outdoor units.
• Check outdoor P .C. board (I/F) error.
• Check model setup for outdoor I/F service P .C. board.
• Check connection of UART communication connector.
• Check Comp. IPDU, fan IPDU, and I/F P .C. board error.
Note)
UART: Universal Asynchronous Receiver Transmitter
n Outside device is connected to connector (CN80):
1) Check outside device error.
2) Check indoor P .C. board error.
n Outside device is not connected to connector (CN80):
1) Check indoor P .C. board error.
Check indoor (I/F) P .C. board.