90° =--- 0,85 m
ø 60 mm
45° =--- 0,65 m
Fig. 6.12
In the last section, the fumes are expelled
through a vertical section.
Extensions and elbows can be added to ex-
tend the kit's length.
Maximum equivalent length "a+b" (Fig.
6.12) of 15 metres can be achieved utilising
extensions.
Each additional elbow reduces the overall
acceptable length of the flue system as fol-
lows:
45° (60/100 mm) reduce length by 0,5 m.
90° (60/100 mm) reduce length by 1 m.
45° (60 mm) reduce length by 0,65 m.
90° (60 mm) reduce length by 0,85 m.
INSTALLATION
90° =--- 1 m
ø 60/100 mm
45° =--- 0,5 m
6.9
Electric connection
• Unscrew screws "O" and remove the front
panel "P" by pulling it and pushing it to-
wards the top so that it is freed from the
top housing Fig. 6.13.
O
Fig. 6.13
• Identify the terminal block cover lid "Q"
(Fig. 6.14) and open it.
P
- 43 -