11
Fig. 7.32
Fig. 7.33
• Scroll the various parameters using keys
12 or 13 until the letters Pr that alternate
with code 10 are displayed on the LCD
display, indicating that "parameter 10"
(Fig. 7.34) has been activated.
Fig. 7.34
- 62 -
COMMISSIONING
• Press keys 11 and 13 (Fig. 7.32) at the
same time until the value of parameter
10 (30=180 seconds) is displayed on the
13
LCD display (Fig. 7.35).
12
Fig. 7.35
• It is possible to modify parameter 10 by
00=0s to 99=600s using keys 12 or 13
(each increase or reduction by a unit on
the display corresponds to 6 seconds).
• By pressing key 11 (Fig. 7.32) confirma-
tion of the inserted value is obtained.
• Press keys 11 and 12 (Fig. 7.32) at the
same time to exit without changing the
value (return to the parameters list Fig.
7.34).
• Press keys 11 - 12 - 13 (Fig. 7.32) at the
same time for 10 seconds to exit the "pro-
gramming mode".
Programming using the REMOTE control
Act on the programming of the REMOTE
control to select a minimum time between
two ignitions when the boiler functions in
normal on/off heating mode.
• Press button
enter in
for more than 3 seconds to
mode (Fig. 7.36).