Advanced configuration mode (Adnc).
input types, battery voltage, and communications
setting can be changed in the advanced configuration
mode.
Press the up arrow button when Adnc is
displayed to enter the advanced configuration mode.
Engine data input types (Ed). This setting defines the
type of senders used on the generator set engine.
Battery voltage (Bt). This setting toggles between 12
and 24 VDC for the engine starting battery voltage.
Communications setting (Cn). This setting allows the
user to set the controller for communication with
optional meters, which are available for marine and
mobile units only.
4.5.3
Voltage and Frequency
Adjustments
The flowchart in Figure 4-12 outlines the procedures for
using the ADC controller to adjust the output voltage and
engine speed (frequency). Voltage and/or frequency
adjustments
may
be
replacement or other service procedures.
TP-6196 10/09
The data
required
after
controller
The generator set must be running during these
adjustments.
Use a multimeter to measure the
generator set output voltage and frequency during
adjustments.
Refer to Sections 6.7.2, Voltage
Adjustment, and 6.9.5, Frequency Adjustment, for
instructions to measure the output voltage and
frequency.
Note: Be sure to save your settings before exiting the
configuration mode. The controller reverts to the
last saved settings when the master switch is
moved to the OFF/RESET position.
4.5.4

Controller Application Program

The ADC 2100 application program version number is
displayed on the LED screen during the key sequence to
enter the configuration mode. Hold the Select button
and move the generator set master switch to the RUN
position.
After about 5 seconds, the application
program version number will be displayed on the
controller display. For example, 01.04 will be displayed
for program version 1.04.
The DC 2200 controller application program version
number is displayed at controller powerup.