Kohler 8.5RES Service Manual page 80

Residential/commercial generator sets
Hide thumbs Also See for 8.5RES:
Table of Contents

Advertisement

1
2
See
Detail
2
3
Controller Box Detail
1. Controller box location
2. Line circuit breaker
3. Load connection terminal L0
Figure 6-12 Circuit Breaker and L0 Terminal Location
4. Follow the controller instructions to step to the
voltage gain adjustment menu. Adjust the voltage
gain (parameter 2P) until the light flicker minimizes.
Save the settings.
5. Check and readjust the voltage if necessary.
6. Set the voltmeter to measure frequency. Adjust the
engine speed to the cut-in frequency shown in
Figure 6-13 by adjusting the engine governor
speed (parameter 4P) through the ADC controller.
See Section 4.5.
Frequency
Cut-In Frequency
60 Hz
57.5 Hz
50 Hz
47.5 Hz
Figure 6-13 Cut-In Frequencies
80
Section 6 Component Testing and Adjustment
1. Measure voltage across circuit breaker terminals L0 and L1,
L2, or L3
Figure 6-14 Voltage Measurement, Three-Phase
7. Set the voltmeter to measure voltage. Adjust the
volts/Hz (parameter 3P) until the voltage level
measured by the voltmeter begins to drop. When
set, the generator (as load is applied) attempts to
maintain normal output until the engine speed
drops below the cut-in frequency set in step 6.
Note: See Section 6.7.3 for more information on
8. Set the voltmeter to measure frequency. Adjust the
engine speed to the operating frequency (50 or
60 Hz) by adjusting the engine governor speed
GM57149
(parameter 4P) through the ADC controller.
9. Readjust the voltage gain (parameter 2P) until the
light flicker minimizes, if necessary.
10. Check the voltage.
(parameter 1P), if necessary.
11. Save the settings as instructed in Section 4.5.
Note: The controller will revert to the previous
12. Stop the generator set.
L0 L1 L2 L3
Models
the volts/Hz (droop) adjustment.
Readjust the voltage
settings at the next startup if the changes are
not saved.
1
GM66010
TP-6196 10/09

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

12resm112res12tres12resl12resnt

Table of Contents