5.8 Voltage Connections

Single-phase generator sets are available from the
factory connected for 120/240 volt 60 Hz.
Figure 5-10 for the factory connections. The generator
sets covered in this document are not reconnectable.
LO (Neutral)
Ground
Load
Side
Line
Side
4
3
2
1
Stator Leads
60 Hz
L0-L1
120 volt
120 volt
L0-L2
240 volt
L1-L2
Figure 5-10 120/240 Volt, 3-Wire Configurations

5.9 Voltage Adjustments

WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Testing live electrical circuits.
current can cause severe injury or death. Have trained and
qualified personnel take diagnostic measurements of live
circuits. Use adequately rated test equipment with electrically
insulated probes and follow the instructions of the test
equipment manufacturer when performing voltage tests.
Observe the following precautions when performing voltage
tests: (1) Remove all jewelry. (2) Stand on a dry, approved
electrically insulated mat. (3) Do not touch the enclosure or
components inside the enclosure. (4) Be prepared for the
system to operate automatically.
(600 volts and under)
TP-6881 7/15
See
LO
GRD
L2
L1
Factory two-pole
circuit breaker
TP-5867
Moving parts.
Hazardous voltage or
Short circuits.
Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
Note: See
Section
3.7
instructions.
Voltage Adjustments Using SiteTech
The SiteTech parameters used to adjust the voltage are
shown in Figure 5-11.
SiteTech Group
Genset System Configuration
Voltage Regulator
Figure 5-11 SiteTech Parameters for Voltage
1
1. Voltage regulator parameter group
Figure 5-12 Voltage Regulator Parameter Group in
SiteTech
Section 5 Component Testing and Adjustment
Do not contact electrical
for
voltage
calibration
Parameter
Genset System Voltage
Average Voltage Adjustment
Volts per Hertz Slope
Volts per Hertz Cut-in
Frequency
Voltage Regulator Gain
83