Top Vent - Horizontal Termination
V
Minimum
1
Elbow only
NOT ALLOWED
1 ft.
30,5 cm
2 ft.
2 ft.
61,0 cm
4 ft.
3 ft.
91,4 cm
8 ft.
4 ft.
1,22 m
10 ft.
5 ft.
1,52 m
16 ft.
V
+ H
= 30 ft. (9,14 m) Maximum
1
1
Note: A 15,2 cm section of straight fl ue must
be attached to the fi replace before a 90° elbow.
USE SLP SERIES COMPONENTS ONLY
Figure 7.4
H
Maximum
1
61,0 cm
1,22 m
2,44 m
3,05 m
4,87 m
Example: DVP pipe 3 ft. (91,4 cm) min. vertical = 11 ft. (3,35 m) max. horizontal
Heat & Glo • SL350TRSI-N-CE, SL350TRSI-PB-CE • 2033-980 Rev. L • 3/14
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles
between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around
• Install wall shield and ceiling fi restops as speci-
Failure to keep insulation or other material away
from vent pipe may cause fi re.
SLP pipe 7 ft. (2,13 m) min. vertical = 11 ft. (3,35 m) max. horizontal
H
1
WARNING
venting and fi restop systems.
fi ed.
V
1
27

Advertisement