Cabinet Construction; Countertop Preparation - Electrolux FGES3065P series Service Manual

Table of Contents

Advertisement

Direct Electrical Connection to the Circuit
Breaker, Fuse Box or Junction Box
If the appliance is connected directly to the circuit
breaker, fuse box or junction box, use flexible, armored
or nonmetallic sheathed copper cable (with grounding
wire). Supply a U.L. listed strain-relief at each end of
the cable. At the appliance end, the cable goes through
the Direct Connection Hole (see
Cord Mounting Plate. Wire sizes (copper wire only)
and connections must conform to the rating of the
appliance.
Where local codes permit connecting the
appliance-grounding conductor to the neutral
(white) wire (see
Figure
1. Be sure that no power is supplied on the cable from
residence.
2. Remove the grounding strap from the terminal block
and from the appliance frame.
3. In the circuit breaker, fuse box or junction box:
a) Connect the green (or bare copper) wire, the
white appliance cable wire, and the neutral (white)
wire together.
b) Connect the 2 black wires together.
c) Connect the 2 red wires together.
Cable from Residence
Neutral
(white) Wire
Red
Wires
Green
(or Bare Copper)
Wire
Cable from
Appliance
Figure 5 - 3-Wire (Grounded Neutral) Electrical
System (Example: Junction Box)
Where local codes DO NOT permit connecting
the appliance-grounding conductor to the neutral
(white) wire, or if connecting to 4-wire electrical
system (see
Figure
6):
1. Be sure that no power is supplied on the cable
from residence.
2. Remove the grounding strap from the terminal
block and from the appliance frame.
3. In the circuit breaker, fuse box or junction box:
a) Connect the white appliance cable wire to the
neutral (white) wire.
b) Connect the 2 black wires together.
c) Connect the 2 red wires together.
d) Connect the green (or bare copper) grounding
wire to the grounding wire of the circuit breaker,
fuse box or junction box.
Figure
4) on the
5):
Black
Wires
Junction
Box
White Wire
U.L.-listed Conduit
Connector (or CSA
listed)
Section 2 Installation Instructions
Cable from Residence
Green (or Bare
Copper) Wire
Red
Wires
Green (or Bare
Copper) Wire
Junction
Box
Cable from
Appliance
Figure 6 – 4-Wire Electrical System
(Example: Junction Box)
6.

Cabinet Construction

6.1
To eliminate the risk of burns
or fire by reaching over heated surface units, do not
have cabinet storage space above the range. If there
is cabinet storage space above range, reduce risk
by installing a range hood that projects horizontally
a minimum of 5" (12,7 cm) beyond the bottom of the
cabinet.
6.2

Countertop Preparation

• The cooktop sides of the range fit over the cutout
edge of your countertop.
• If you have a square finish (flat) countertop, no
countertop preparation is required. Cooktop sides lay
directly on edge of countertop.
• Formed front-edged countertops must have
molded edge shaved flat 3/4" (1,9 cm) from each
front corner of opening
• Tile countertops may need trim cut back 3/4" (1,9
cm) from each front corner and/or rounded edge
flattened
(Figure
7).
• If the existing cutout width is greater than 30
1/16" (76,4 cm), reduce the ¾" (1,9 cm) dimension.
Min.
Cutout
Width
Figure 7
White Wire
Black
Wires
White Wire
U.L.-listed Conduit
Connector (or CSA
listed)
(Figure
7).
Formed or tile countertop
trimmed ¾" (1,9 cm) back at
front corners of countertop
opening.
2-7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cges3065p seriesFpes3085p seriesCpes3085p series

Table of Contents