Download Print this page

Samsung MWR-WE10N Installation Manual page 7

Hide thumbs Also See for MWR-WE10N:

Advertisement

Wired Remote Controller Installation
Wired Remote Controller Installation
3. Using more than two screws, firmly affix the rear cover of the remote controller to the wall, and then connect
the communication & power cable[(F3,F4) or (3, 4)], making sure these cables have reasonable length,
to the terminal at the back of the cover.
10mm(0.4inch) or more
10mm(0.4inch) or more
10mm(0.4inch)
or more
50mm(2inch) or more
Rear cover
Before fixing the rear cover, secure at least
10mm(0.4inch) space of upper side, left side,
right side, and 50mm(2inch) space
of bottom side.
4. Reassemble your Wired Remote Controller.
• Align the controller with the upper groove first, and insert it by turning it downward as
shown in the figure.
After assembly, check and confirm that no wires are stuck in the gap between the rear and
front cover.
• When installing a Wired Remote Controller by using a cable longer than 10 m(32.80 ft), you must install the
communication cable and the power cable separately. (Electrical interference can cause your Wired Remote Controller
to malfunction.)
• When installing your Wired Remote Controller on the wall, consider the size of the wire hole, and select a wire with
a proper thickness.
• Wire that is connectable to Wired Remote Controller PCB.
- If you install the Wired Remote Controller by reclaiming, install it according to U-terminal cable specification.
- If you install the Wired Remote Controller by using two pieces of PVC wire, remove the 30cm(12inch) of the
sheath of the cable and install it only with the two pieces of wires. (Recommended specification: AWG21)
• The following are the specs of the compression ring terminal connected to your Wired Remote Controller PCB.
• Screws on the PCB terminal must be tightened with less than 6N-cm tightening torque. If the tightening torque is
greater, it may damage the screw thread.
6
Screw hole
You must fit the screws into
the screw holes.
Range of Permitted Wires
AWG
22~16
Maximum distance for connecting communication and
power cable: 100 m(3.280 ft)
Indoor unit
Wire (not supplied)
Wired Remote
Controller
Do not tighten the screws on the
PCB terminal with excessive force.
Rated
Stud
Basic Size [mm (inch)]
Size
Size
2
2
mm
mm
mm
t
øD
G
2
2
(inch
)
(inch
)
(inch)
0.25~1.65
1.5
3
0.7
3.8
10.0
(0.0003 ~
(0.0023)
(0.1181)
(0.0275)
(0.1496)
(0.3937)
(0.1771)
0.0025)
PCB terminal
Front cover
E
F
W
L
4.5
6.5
6.0
21.2
(0.2559)
(0.2362)
(0.8346)