(C) Power transistor inspection procedure
[Use a tester with a needle indicator for the inspection. (Do not use a digital tester. Check in the AC 300 volt range.)]
(1) If there is a self-diagnosis display, inspect the compressor system (burns, wiring mistakes, etc.) If no problems are found, check the
output of the power transistor.
(2) Output inspection procedure
Disconnect the terminals for the compresseor.
If an output such as the one shown in the figure on the below can be measured, the power transistor and the circuit board for the
outdoor unit are normal.
Output voltage
(ACV)
0
Operation SW ON

(10) How to make sure of wireless remote controller

8~10 sec.
1 sec.
3 min.
Measure in this section
1 sec.
3 min.
The figare below shows the SRK series.
58
-
-
'09•SRK-DB-087D
'10 • SCM-SM-094
(Example)
RUN light : ON
TIMER light: 2 time flash