Outdoor Air Temperature Sensor Anomaly - Mitsubishi Heavy Industries SRK20ZJX-S Service Manual

Hide thumbs Also See for SRK20ZJX-S:
Table of Contents

Advertisement

Error code
Remote controller:
E38
1. Applicable model
All models
2. Error detection method
Detection of anomalously low
temperature (resistance) on
outdoor air temperature sensor
3. Condition of Error displayed
• When the temperature sensor
detects -55 °C or lower for 5
seconds continuously within
2 minutes to 2 minutes 20
seconds after the compressor
ON, the compressor stops.
After 3-minutes delay, the
compressor starts again
automatically, but if this
anomalous temperature is
detected 3 times within 40
minutes.
• When -55 °C or lower is
detected for within 20 second
after power ON.
4. Presumable cause
• Defective outdoor main PCB
• Broken sensor harness or
temperature sensing section
(Check molding.)
• Disconnected wire connection
(connector)
Note:
LED
Green
Red
Indoor
Keeps flashing Stays OFF
Outdoor
8 times flash
5. Troubleshooting
Diagnosis
Is
the suction pipe
temperature sensor connector
connected properly?
YES
Is the
characteristics of the
suction pipe temperature
sensor
OK?
Temperature-resistance characteristics
(Broken wire)
15
10
5
(Shot circuit)
0
10
20
Temperature (°C)
103
-
Content
Outdoor air temperature
sensor anomaly
NO
For the characteristics of suction pipe
temperature sensor, see the following graph.
NO
YES
5k at 25°C
30
40
50
-
'10 • SCM-SM-094
Countermeasure
Correct connector.
Defective outdoor air
temperature sensor
Replace.
Defective outdoor main
PCB Replace.
(Defective outdoor air
temperature sensor input
circuit)