To ensure proper unit grounding, the ground wire should run from
the furnace ground screw located inside the furnace junction box
all the way back to the electrical panel. NOTE: Do not use gas
piping as an electrical ground. To confirm proper unit grounding,
turn off the electrical power and perform the following check.
1. Measure resistance between the neutral (white) connection
and one of the burners.
2. Resistance should measure 10 ohms or less.
This furnace is equipped with a blower door interlock switch which
interrupts unit voltage when the blower door is opened for servic-
ing. Do not defeat this switch.
24 V
T
W
OLT
HERMOSTAT
Low voltage connections can be made through either the right or
left side panel. Thermostat wiring entrance holes are located in the
blower compartment. The following figure shows connections for a
"heat/cool system".
This furnace is equipped with a 40 VA transformer to facilitate use with most cooling equipment. Consult the wiring diagram, located
on the blower compartment door, for further details of 115 Volt and 24 Volt wiring.
As shipped, the furnace S1-1 switch is OFF; S1-2 switch is ON. This is the correct position to use a single stage heating
thermostat with auto timing transition to high fire.
R
R
Y
C
Remote Condensing Unit
(Single-Stage Cooling)
Thermostat - Single -Stage Heating
with Single-Stage Cooling
NOTE: To apply a single-stage Heating
Thermostat, the thermostat selector
switch on the Integrated Control Module
must be set on single-stage.
Figure 24
IRING
Furnace
Integrated
Control
Module
Remote Condensing Unit
(Single-Stage Cooling)
Thermostat - Two-Stage Heating
with Single-Stage Cooling
T
O PREVENT PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK
DISCONNECT ELECTRICAL POWER BEFORE INSTALLING OR SERVICING THIS
.
UNIT
HIGH VOLTAGE !
T
O AVOID THE RISK OF INJURY
,
DEATH
THE FURNACE MUST BE ELECTRICALLY
GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN
THEIR ABSENCE
N
E
ATIONAL
T
O AVOID THE RISK OF INJURY
FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH
LOCAL CODES OR
N
E
ATIONAL
W
IRE ROUTING MUST NOT INTERFERE WITH CIRCULATOR BLOWER
OPERATION
R
R
Y
C
Figure 25
22
WARNING
WARNING
,
ELECTRICAL SHOCK OR
,
WITH THE LATEST EDITION OF THE
C
.
LECTRIC
ODE
WARNING
,
ELECTRICAL SHOCK OR DEATH
,
,
IN THEIR ABSENCE
WITH THE LATEST EDITION OF THE
C
.
LECTRICAL
ODE
IMPORTANT NOTE
,
FILTER REMOVAL OR ROUTINE MAINTENANCE
Y2
Furnace
Integrated
Y
Control
Module
Y2
Remote Condensing Unit
(Two-Stage Cooling)
Thermostat - Two-Stage Heating with
Two-Stage Cooling
Thermostat Wiring Diagrams
Figure 26
,
,
THE
.
W1
W2
Furnace
W1
W2
Integrated
Control
Module

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gmec96

Table of Contents