For installations above 7000 feet, please re-
fer to the furnace Specification Sheets for
required kit(s).
Contact the distributor for a tabular listing of
appropriate manufacturer's kits for propane
gas and/or high altitude installations. The
indicated kits must be used to insure safe and
proper furnace operation. All conversions must
be performed by a qualified installer, or ser-
vice agency.
V
/F
P
& C
ENT
LUE
IPE
A condensing gas furnace achieves its high level of efficiency by
extracting almost all of the heat from the products of combustion
and cooling them to the point where condensation takes place.
Because of the relatively low flue gas temperature and water con-
densation requirements, PVC pipe is used as venting material.
In addition to PVC and ABS pipe and fittings, Innoflue
Centrotherm Eco Systems and PolyPro
also approved vent and combustion air materials for installa-
tions in the U.S.A. and Canada. Manufacturers Installation
instructions for these products must be followed. These products have specific instructions for installing, joining and termi-
nating. Do not mix materials or components of one manufacturer with materials or components of another manufacturer.
All furnaces are built with 2" vent / intake pipe and connectors. For furnaces requiring installation of 3" pipe, the transition
from 2" to 3" should be done as close to the furnace as practically possible.
This furnace must not be connected to Type B, BW, or L vent or vent connector, and must not be vented into any portion of a factory
built or masonry chimney except when used as a pathway for PVC as described later in this section. Never common vent this appliance
with another appliance or use a vent which is used by a solid fuel appliance. Do not use commercially available "no hub connectors"
other than those shipped with this product.
It is the responsibility of the installer to follow the manufacturers' recommendations and to verify that all vent/flue piping and
connectors are compatible with furnace flue products. Additionally, it is the responsibility of the installer to ensure that all piping and
connections possess adequate structural integrity and support to prevent flue pipe separation, shifting, or sagging during furnace
operation.
D
C
: N
UAL
ERTIFICATION
ON
This furnace is dual certified and may be installed as a non-direct vent (single pipe) or direct vent (dual pipe) appliance. A non-direct
vent installation requires only a vent/flue pipe, while a direct vent installation requires both a vent/flue pipe and a combustion air
intake pipe. Refer to the appropriate section for details concerning piping size, length, number of elbows, furnace connections, and
terminations.
M
J
M
ATERIALS AND
OINING
Two-three-inch nominal diameter PVC Schedule 40 pipe meet-
ing ASTM D1785, PVC primer meeting ASTM F656, and PVC
solvent cement meeting ASTM D2564 specifications must be
used. Fittings must be DWV type fittings meeting ASTM D2665
and ASTM D3311. Carefully follow the manufacturer's instruc-
tions for cutting, cleaning, and solvent cementing of PVC.
The use of Schedule 40 PVC or ABS cellular core (Foam Core) plastic pipe is also acceptable as a flue/vent and intake pipe
material. PVC primer meeting ASTM F656 and PVC solvent cement meeting ASTM D2564 specifications must be used. Fittings
must be DWV type fittings meeting ASTM D2665 and ASTM D3311. Carefully follow the manufactures instructions for cutting,
cleaning and solvent cementing of PVC.
For Canadian installations; all PVC pipe, fittings and joining materials must be UL S636 listed.
GAS
NATURAL
PROPANE
*supports both Honeywell and White-Rodgers 2-stage valves
(1) FOR USE WITH ALL MODELS EXCEPT *MEC960302BN**
(2) FOR USE WITH ONLY *MEC960302BN** MODEL
A
P
OMBUSTION
IR
IPE
by M&G Duravent are
®
-D
/D
V
IRECT
IRECT
ENT
ETHODS
ALTITUDE
KIT
ORIFICE
#45 (1)
NONE
#50 (2)
0 - 7000
LPM-08* (1) 1.25MM (1)
LPM-30* (2)
#57 (2)
F
AILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN BODILY
. C
INJURY OR DEATH
GIVEN IN THIS SECTION
U
PON COMPLETION OF THE FURNACE INSTALLATION
INSPECT THE ENTIRE FLUE SYSTEM BOTH INSIDE AND OUTSIDE OF THE
FURNACE TO ASSURE IT IS PROPERLY SEALED
by
®
SYSTEM CAN RESULT IN SERIOUS PERSONAL INJURY OR DEATH DUE TO
EXPOSURE TO FLUE PRODUCTS
T
O AVOID BODILY INJURY
MUST BE KEPT AWAY FROM ALL IGNITION SOURCES
,
FLAMES
AND EXCESSIVE HEAT
A
VOID BREATHING CEMENT VAPORS OR CONTACT WITH SKIN AND
.
EYES
11
MANIFOLD PRESSURE
HIGH STAGE LOW STAGE
3.5" w.c.
1.9" w.c.
10.0" w.c.
6.0" w.c.
WARNING
AREFULLY READ AND FOLLOW ALL INSTRUCTIONS
.
WARNING
. L
EAKS IN THE FLUE
,
INCLUDING CARBON MONOXIDE
WARNING
,
,
FIRE OR EXPLOSION
SOLVENT CEMENTS
)
AS THEY ARE COMBUSTIBLE LIQUIDS
PRESSSURE
SWITCH CHANGE
NONE
NONE
,
CAREFULLY
.
(
.
.,
,
I
E
SPARKS
OPEN
.
/
OR