Table of Contents

Advertisement

I
NSTALLATION
*MSS9* & *CSS9*
S
-S
INGLE
TAGE
(Type FSP CATEGORY IV Direct
or Non Direct Vent Air Furnace)
These furnaces comply with requirements em-
bodied in the American National Standard / Na-
tional Standard of Canada ANSI Z21.47·CSA-2.3
Gas Fired Central Furnaces.
s a professional installer you have an obligation to know
A
the product better than the customer. This includes all safety
precautions and related items.
Prior to actual installation, thoroughly familiarize yourself
with this Instruction Manual. Pay special attention to all
safety warnings. Often during installation or repair it is
possible to place yourself in a position which is more
hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product
safely and to know it well enough to be able to instruct a
customer in its safe use.
Safety is a matter of common sense...a matter of thinking
before acting. Most dealers have a list of specific good
safety practices...follow them.
The precautions listed in this Installation Manual are intended
as supplemental to existing practices. However, if there is
a direct conflict between existing practices and the content
of this manual, the precautions listed here take precedence.
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION.
IOG-2009E
10/2015
I
NSTRUCTIONS FOR
G
F
AS
URNACE
Installer:
Affix all manuals
adjacent to the unit.
5151 San Felipe Suite 500
Houston, TX 77056
www.goodmanmfg.com • www.amana-hac.com
© 2014 - 2015 Goodman Manufacturing Company, L.P.
is a registered trademark of Maytag Corporation or its related companies
and is used under license. All rights reserved.

TABLE OF CONTENTS

S
C
.......................................... 3
............................................ 4
............................................. 5
P
A
............................................. 5
L
R
& C
..................................... 8
.......................................... 9
C
& V
A
I
P
............................................ 9
H
A
& C
.......................................... 10
F
C
P
........................................ 10
..................................................... 10
A
E
G
................................................... 10
........................................... 10
P
G
/H
A
I
V
/F
P
ENT
LUE
IPE
D
C
-D
UAL
ERTIFICATION
IRECT
P
V
/F
C
ROPER
ENT
LUE AND
OMBUSTION
........................................ 12
V
V
/I
T
F
ENT
NTAKE
ERMINATIONS
V
V
V
.......................................... 18
C
D
L
& D
......................................... 19
V
..................................... 20
L
...................................... 20
EFT
U
I
H
.................................... 20
U
I
H
PFLOW
NSTALLED
...................................... 21
...................................... 21
..................................... 21
C
M
I
OUNTERFLOW
ODEL
NSTALLED
..................................... 22
WITH
C
M
I
OUNTERFLOW
ODEL
NSTALLED
...................................... 22
.................... 4
......................... 6
................................... 7
R
..................... 9
....................... 10
T
L
................ 10
L
C
.............. 10
....................... 10
A
P
......................... 11
IR
/D
V
................. 11
.............................. 11
A
IR
.............................. 13
.............................. 13
I
OR
NSTALLATION
......................... 17
................................. 18
T
.......................... 18
................................... 19
.......................... 19
ORIZONTALLY
V
.................... 21
H
ORIZONTALLY
H
ORIZONTALLY
...... 12

Advertisement

Table of Contents
loading

Summary of Contents for Goodman GMSS96

  • Page 1: Table Of Contents

    5151 San Felipe Suite 500 Houston, TX 77056 IOG-2009E www.goodmanmfg.com • www.amana-hac.com 10/2015 © 2014 - 2015 Goodman Manufacturing Company, L.P. is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
  • Page 2 ......... 23 ........38 LECTRICAL ONNECTIONS AFETY IRCUIT ESCRIPTION ..........23 ......... 38 IRING ARNESS NTEGRATED ONTROL ODULE 115 V ........23 ..........38 ONNECTIONS RIMARY IMIT ........24 ..........38 UNCTION ELOCATION UXILIARY IMIT 24 V ........24 ..........38 HERMOSTAT IRING OLLOUT...
  • Page 3: Afety Onsiderations

    AFETY ONSIDERATIONS WARNING Adhere to the following warnings and cautions when install- O PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER ing, adjusting, altering, servicing, or operating the furnace. INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE To ensure proper installation and operation, thoroughly read REFER TO THIS MANUAL OR ADDITIONAL ASSISTANCE OR this manual for specifics pertaining to the installation and...
  • Page 4: Shipping Inspection

    RISQUE D'EMPOISONNEMENT AU MONOXYDE DE CARBONE Advertencia especial para la instalación de calentadores ó manejadoras de aire en áreas cerradas como estacionamientos ó cuartos de servicio. Cette ventilation est nécessaire pour éviter le danger d'intoxication Las emisiones de monóxido de carbono pueden circular a través au CO pouvant survenir si un appareil produisant du monoxyde del aparato cuando se opera en cualquier modo.
  • Page 5: T O The Installer

    3. Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat step 2 before touching control or wires.
  • Page 6: Ocation Equirements Onsiderations

    • If the unit is to be installed in an attic, the passageway to and the service area around the unit must have flooring. To ensure proper furnace operation, install, operate and maintain the furnace in accordance with these installation and operation instructions, all local building codes and ordinances.
  • Page 7: Clearances And Accessibility

    paint removers varnishes hydrochloric acid cements and glues antistatic fabric softeners for clothes dryers masonry acid washing materials • Seal off a non-direct vent furnace if it is installed near an area frequently contaminated by any of the above substances. This protects the non-direct vent furnace from airborne contaminants.
  • Page 8: Existing Furnace Removal

    NOTE: In addition to the required clearances to combustible materials, a minimum of 24 inches service clearance must be available in front of the unit. SIDE SIDE SIDE BOTTOM BOTTOM Upflow Counterflow Horizontal Figure 1 A furnace installed in a confined space (i.e., a closet or utility room) must have two ventilation openings with a total minimum free area of 0.25 square inches per 1,000 BTU/hr of furnace input rating.
  • Page 9: Thermostat Location

    If resizing is required on any portion of the venting system, use the appropriate table in Appendix G in the latest edition of the National Fuel Gas Code ANSI Z223.1 and/or CSA B149.1-05 Installation Codes. HERMOSTAT OCATION The thermostat should be placed approximately five feet from the floor on a vibration-free, inside wall in an area having good air circulation.
  • Page 10: Orizontal Pplications Onsiderations

    be attached to the back of the furnace. Contact your distributor for proper airflow requirements and number of required ductwork connections. Refer to “Recommended Installation Positions” figure for appropriate installation positions, ductwork connections, and resulting airflow arrangements. & C ORIZONTAL PPLICATIONS ONSIDERATIONS When installing a furnace horizontally, additional consideration...
  • Page 11: Combustion

    High altitude installations may require both a pressure switch and an orifice/spring change. These changes are necessary to com- WARNING pensate for the natural reduction in the density of both the gas OSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH MAY fuel and the combustion air at higher altitude.
  • Page 12: Termination Locations

    The use of Schedule 40 PVC cellular core DWV meeting ASTM F891-1 or ABS cellular core (Foam Core) plastic pipe is also acceptable as a flue/vent and intake pipe material. PVC primer meeting ASTM F656 and PVC solvent cement meeting ASTM D2564 specifications must be used.
  • Page 13: Canadian Venting Requirements

    • The vent termination of a non-direct vent application must Non-Direct Vent terminate at least 4 feet below, 4 feet horizontally from, or 1 & Direct Vent foot above any door, window, or gravity air inlet into any Vent/Flue Terminations building.
  • Page 14: Alternate Combustion Air Provision

    COMBUSTION AIR INTAKE OPTION: The RF000142 coupling (Figure 8B) can be secured VENT-DRAIN directly to the furnace intake coupling if condensation is a concern. If the RF000142 is used on the combustion air inlet, it must be installed with the arrow pointing up. It should be noted, the combustion air will actually be moving in a direction opposite of the arrow on the RF000142 coupling.
  • Page 15: Non-Direct Vent Piping

    4. Use a knockout tool to create a 3" diameter hole CAUTION 5. Install combustion air flange and secure with screws removed in step one. E SURE NOT TO DAMAGE INTERNAL WIRING OR OTHER COMPONENTS WHEN REINSTALLING COUPLING AND SCREWS IRECT INGLE IPING...
  • Page 16 DOWN VENTING UPFLOW MODEL FURNACES ONLY Use alternate vent & combination air locations 6’ MAX. Vent Pipe Combustion Air Pipe Both Pipes Terminated Outside Structure Field Supplied Drain Tee on Vent Pipe 1/4” per foot min. slope Condensate trapped to prevent flue gas from escaping and routed to field supplied condensate disposal All piping and fittings must be joined per material manufacturer’s specifications...
  • Page 17: Of Multiple Direct Vent Furnaces

    IRECT IPING Direct vent installations require both a combustion air intake and a vent/flue pipe. The pipes may be run horizontally and exit through the side of the building or run vertically and exit through the roof of the building. The pipes may be run through an existing unused chimney;...
  • Page 18: Ondensate Rain Ines Rain Rap

    minimum clearances between the exhaust vent and air intake terminations of adjacent units as with the exhaust vent and air intake terminations of a single unit. 90° ELBOWS 3”MIN 24”MAX 12” MIN SEPARATION 3”-24” BETWEEN PIPES 3” MIN 12" MIN. ABOVE HIGHEST ANTICIPATED SNOW LEVEL 12”...
  • Page 19: General Drain Information

    • The drain trap supplied with the furnace must be used. • The drain trap must be primed at time of installation. • The drain line between furnace and drain location must meet local and nation codes. • The drain line between furnace and drain location must maintain a 1/4 inch per foot downward slope toward the drain. •...
  • Page 20: Drain Exiting Right Side

    RAIN XITING IGHT 1. Locate and Install the 45º pipe / hose drain coupling from the outside of the cabinet (barbed end goes in the cabinet) through hole in the right side of the cabinet and secure with two field supplied #8 self- tapping screws (see Figure 22).
  • Page 21: Model

    PFLOW ODEL NSTALLED ORIZONTALLY WITH Minimum 5 1/2" clearance is required for the drain trap beneath the furnace. *Also see Front Cover Pressure Switch Tube Location on page 10. 1. Remove the clamps from the two drain tubes on the trap. 2.
  • Page 22: Side

    7. Line up the trap mounting holes with the pre-drilled holes in the furnace and secure with 2 screws removed in step 8. Refer to Field Supplied Drain section for instructions on field supplied / installed drain on outlet of furnace trap. OUNTERFLOW ODEL NSTALLED...
  • Page 23: Electrical Connections

    13. Locate another hose #5 cut a 5.25" straight section and discard the radius end. 14. Connect the 5.25’ straight section to the 100º elbow and the PVC pipe and secure with red clamps. 15. Mate trap inlets and hoses and secure with silver clamps, drain trap outlet must point to the original bottom of the furnace.
  • Page 24: Junction Box Relocation

    The integrated control module single humidifier terminal (HUM) is energized with 115 volts whenever the induced draft blower is energized. This terminal can also be used to provide 115 volt power to a humidifier transformer. The remaining primary transformer wire would be connected to the Line N on the control board. The integrated control module electronic air cleaner terminals (EAC) are energized with 115 volts whenever the circulator blower is energized.
  • Page 25: Gas Supply And Piping

    bined gas furnace and heat pump installation which uses an out- IMPORTANT NOTE door temperature sensor to determine the most cost efficient means of heating (heat pump or gas furnace). IRE ROUTING MUST NOT INTERFERE WITH CIRCULATOR BLOWER OPERATION FILTER REMOVAL OR ROUTINE MAINTENANCE Strictly follow the wiring guidelines in the fossil fuel kit installation instructions.
  • Page 26: Gas Piping Connections

    propane gas spring from an appropriate manufacturer’s propane gas conversion kit. Taps for measuring the gas supply pressure and manifold pressure are provided on the valve. The gas valve has a manual ON/OFF control located on the valve WARNING itself. This control may be set only to the “ON” or “OFF” position. Refer to the lighting instructions label or Startup Procedure &...
  • Page 27 • Use listed gas appliance connectors in accordance with their instructions. Connectors must be fully in the same room as the furnace. • Protect connectors and semirigid tubing against physical and thermal damage when installed. Ensure aluminum-alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry, plaster, or insulation, or subjected to repeated wetting by liquids such as water (except rain water), detergents, or sewage.
  • Page 28: Propane Gas Tanks And Piping

    The gas piping may enter the left or right side of the furnace cabinet. The installer must supply rigid pipe long enough to reach the outside of the cabinet to seal the grommet cabinet penetration. A semi-rigid connector to the gas piping can be used outside the cabinet per local codes.
  • Page 29: Circulating Air & Filters

    & F IRCULATING ILTERS UCT WORK Duct systems and register sizes must be properly designed for the CFM and external static pressure rating of the furnace. Design the ductwork in accordance with the recommended methods of “Air Conditioning Contractors of America” Manual D. Install the duct system in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air Heating and Ventilating Systems.
  • Page 30: Ottom Eturn Ir Pening Pflow

    Example: static reading from return duct = -.1" w.c. static reading from supply duct = .3" w.c. total external static pressure on this system = .4" w.c. NOTE: Both readings may be taken simultaneously and read directly on the manometer if so desired. If an air conditioner coil or Electronic Air Cleaner is used in conjunction with the furnace, the readings must also include theses components, as shown in the following drawing.
  • Page 31: Ir Duct Work

    ILTERS ECTION EFORE NSTALLING ETURN UCT WORK Filters must be used with this furnace. Discuss filter maintenance with the building owner. Filters do not ship with this furnace, but must be provided, sized and installed externally by the installer. Filters must comply with UL900 or CAN/ULCS111 standards. Damage or repairs due to the installation of the furnace without filters is not covered under the warranty.
  • Page 32 Air Cleaner Maximum Filter (Media) Air Cleaner Part Number Installation Location Heating Airflow Dimensions Family Si de or bottom return 1200 CFM 16 i n X 20 i n x 5¼" AM11-1620-5 Si de or bottom return 1600 CFM 16 i n X 25 i n x 5¼" AM11-1625-5 AM11-5 Si de or bottom return...
  • Page 33: Bottom Return Air Opening

    ORIZONTAL NSTALLATIONS Filters must be installed in either the central return register or in the return air duct work. & A TARTUP ROCEDURE DJUSTMENT Furnace must have a 115 VAC power supply properly connected and grounded. Proper polarity must be maintained for correct operation.
  • Page 34: Gas Supply Pressure Measurement

    UPPLY RESSURE EASUREMENT RESSURE The line pressure supplied to the gas valve must be within the range specified below. The supply pressure can be measured at the gas valve inlet pressure tap or at a hose fitting installed in the gas piping drip leg. The supply pressure must be measured with the burners operating.
  • Page 35: Atural Gas Only )

    1. Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace. 2. Turn off all electrical power to the system. 3. Outlet pressure tap connections: White-Rodgers 36J22 valve: Back outlet pressure test screw (inlet/outlet pressure tap) out one turn (counterclockwise, not more than one turn).
  • Page 36: Temperature Rise

    4. Turn ON gas to and relight all other appliances turned off in step 1. Be certain that all appliances are functioning properly and that all pilot burners are operating. EMPERATURE SUPPLY Temperature rise must be within the range specified on the unit rating plate.
  • Page 37: Normal Sequence Of Operation

    LOWER ELAY IMINGS The integrated control module on 96% models provides a selectable heat off delay function. The heat off delay period may be set to 100 or 150 seconds by cutting the jumper on the control module. The delay is factory shipped at 150 seconds but may be changed to suit the installation requirements and/or homeowner preference.
  • Page 38: Operational Checks

    The normal operational sequence in fan only mode is as follows: • R and G thermostat contacts close, initiating a call for fan. • Integrated control module performs safety circuit checks. • Circulator blower is energized on heat speed. • 96% models 115 VAC EAC terminal is energized.
  • Page 39: Maintenance

    integrated control module to electrostatic discharge. This procedure is applicable to both installed and uninstalled (ungrounded) furnaces. 1. Disconnect all power to the furnace. Do not touch the integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground.
  • Page 40: Filters

    • Drainage system. Check for blockage and/or leakage. Check hose connections at and internal to furnace. • Wiring. Check electrical connections for tightness and/or corrosion. Check wires for damage. • Filters. ILTERS ILTER AINTENANCE DIAGNOSTIC CODES Improper filter maintenance is the most com- 1 flash, then pause System lockout mon cause of inadequate heating or cooling...
  • Page 41: Induced Draft And Circulator Blowers

    NDUCED RAFT AND IRCULATOR LOWERS The bearings in the induced draft blower and circulator blower motors are permanently lubricated by the manufacturer. No further lubrication is required. Check motor windings for accumulation of dust which may cause overheating. Clean as necessary. ONDENSATE RAP AND RAIN...
  • Page 42: Troubleshooting Chart

    ROUBLESHOOTING HART Associated Fault Symptoms of Abnormal Cautions & Possible Causes Corrective Action Description(s) Operation LED Code Notes •Assure 115 and 24 volt •Turn power OFF •Furnace fails to •Manual disconnect •No 115 volt power NONE power to furnace prior to repair. operate.
  • Page 43: Troubleshooting Chart

    ROUBLESHOOTING HART Associated Fault Cautions and Symptoms of Abnormal Possible Causes Corrective Action Description(s) Notes Operation LED Code •Circulator blower runs •Check primary/ •Primary or •Faulty pirmary or •Turn power OFF prior auxiliary limit. Replace continuously. No auxiliary limit auxiliary limit switch. to repair.
  • Page 44: Mss92*** & *Css92***A

    *MSS92*** & *CSS92***A* IRFLOW RISE RISE RISE RISE RISE HIGH 1498 1446 1368 1302 1227 1145 1059 1223 1182 1153 1099 1051 *MSS920402BN MED-LO HIGH 1494 1428 1362 1294 1231 1162 1076 1203 1178 1147 1101 1045 *MSS920603BN MED-LO HIGH 1459 1397 1339...
  • Page 45: Mss96*** & *Css96***A

    *MSS96*** & *CSS96***A* IRFLOW RISE RISE RISE RISE RISE HIGH 1478 1418 1354 1290 1208 1129 1040 1299 1265 1225 1167 1112 1033 *MSS960402BN MED-LO 1081 1064 1039 HIGH 1432 1374 1319 1237 1157 1063 1289 1250 1204 1142 1066 *MSS960603BN MED-LO 1080...
  • Page 46: Wiring Diagram *Mss92*** & *Css92***A

    *MSS92*** & *CSS92***A* IRING IAGRAM Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 47: Mss96*** & *Css96***A

    *MSS96*** & *CSS96***A* IRING IAGRAM 115 VAC HOT AND PA RK TER MINALS CO OL-H HEAT-H E AC-H LINE-H Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 48: Special Instructions For Products

    NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE. 5151 San Felipe Suite 500 Houston, TX 77056 www.goodmanmfg.com • www.amana-hac.com © 2014 - 2015 Goodman Manufacturing Company, L.P . is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.

Table of Contents