Goodman GMPN100 Installation & Operating Instructions Manual

Condensing gas furnace gmpn series

Advertisement

INSTALLATION
& OPERATING
INSTRUCTIONS
for GMPN
CONDENSING
GAS FURNACE
(CATEGORY IV)
(U.S. PAT. # 5,437,263)
EPA
POLLUTION
PREVENTER
E FF|CII_NCY
RATING
CERT_FIEO
ama
IF THIS FURNACE
IS INSTALLED
IN AN ENCLOSED
AREA, SUCH AS A GARAGE
OR
UTILITY
ROOM, EITHER ALONE
OR WITH ANY OTHER CARBON
MONOXIDE
PRODUCING
DEVICE
(i.e. ATUOMOBLIE,
SPACE
HEATER,
WATER
HEATER,
ETC.) INSURE THAT THE
ENCLOSED
AREA IS PROPERLY
VENTILATED.
WARNING
CARBON
MONOXIDE
(REFERRED
TO AS CO) CAN CAUSE SERIOUS
PERSONAL
INJURY
I
OR DEATH.
I
WARN
ING
I
THIS FURNACE
IS DESIGN
CERTIFIED
FOR
INSTALLATION
IN BUILDINGS
CONSTRUCTED
I
ON SITE ONLY.
I
Goodman Manufacturing Company, L.P.
IO-151D
1501 Seamist, Houston, Texas 77008
12/01
REPLACEMENT
PARTS

Advertisement

Table of Contents
loading

Summary of Contents for Goodman GMPN100

  • Page 1 WARNING CARBON MONOXIDE (REFERRED TO AS CO) CAN CAUSE SERIOUS PERSONAL INJURY OR DEATH. WARN THIS FURNACE IS DESIGN CERTIFIED INSTALLATION IN BUILDINGS CONSTRUCTED ON SITE ONLY. Goodman Manufacturing Company, L.P. IO-151D 1501 Seamist, Houston, Texas 77008 12/01 REPLACEMENT PARTS...
  • Page 2 SERVICE PARTS DEPARTMENT GOODMAN MANUFACTURING CO., L.P. 1501 SEAMIST HOUSTON, TEXAS 77008 (713) 861 - 2500 The major parts groups are as follows;...
  • Page 3: Table Of Contents

    INDEX WARNINGS & GENERAL INFORMATION LOCATION, CLEARANCES VENTING GAS PIPING TABLE 9-11 CIRCULATING & RETURN AIR 11,12 ELECTRICAL SUPPLY 12, 13 CONTROL VOLTAGE RATING THE FURNACE 14, 15 TIMING THE GAS METER 15, 16 SAFETY CONTROLS 16, 17 CIRCULATING AIR FILTERS 17, 18 TEMPERATURE RISE, MAINTENANCE...
  • Page 4 WHILE CARBON MONOXIDE DETECTORS DO PROVIDE ADDITIONAL PROTECTION, CURRENT LIMITATIONS TO THEIR EFFECTIVENESS REQUIRES THAT YOU OTHERWISE CONTINUE TO FOLLOW APPROPRIATE INSTRUCTIONS LOCATED IN THE "INSTALLATION & OPERATING INSTRUCTIONS" AND "USERS INFORMATION" MANUALS RELATING PROTECTING PERSONS FROM THE RISKS OF CARBON MONOXIDE.
  • Page 5 installed in accordance with the current CAN/CGA-B149.1 & 2 Gas Installation Codes, local plumbing or waste water codes and other applicable codes. Additional helpful publications are available from the NFPA are, NFPA 90A - Installation of Air Conditioning and Ventilating System and NFPA 90B - Warm Air Heating and Air Conditioning System.
  • Page 6: Venting

    A gas furnace must not be installed directly on carpeting, tile, or other combustible materials other than wood flooring. COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE CABINET. THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIAL INCLUDING...
  • Page 7 GMPN080 2" 67.5' 52.5' GMPN100 3" 100' 100' 100' 100' 100' GMPN120 3" 100' 100' 100' 100' 100' Should more elbows be required, subtract 7.5' from the vent length for each elbow used (over 4 as noted above). A maximum of 6 elbows is acceptable.
  • Page 8 DO NOT install the vent pipe in the same chase with the vent from another fuel burning appliance, except with a GMN, GMPN, GSUS, or GSU furnace manufactured by GOODMAN. DO NOT install the vent pipe within six (6) inches of another fuel burning appliance. The drain trap must be easily accessible for checking and / or cleaning.
  • Page 9 drain to the terminal. This will allow the condensate to flow backwards into the drain system and not out the terminal. When penetrating the structure to the outdoors install a sleeve to allow for expansion and contraction. Vertical runs must be supported a minimum of every six (6) feet.
  • Page 10 Both the supply and manifold pressure must be measured with the furnace running using the field supplied pressure tap near the manual shut-off valve and the pressure adjusted if necessary. All gas piping must conform to local codes, or in the absence of local codes, to the National Fuel Gas Code ANSI Z223.1 and / or CAN/CGA...
  • Page 11 The circulating air supply may be taken from; 1) Outside the building, 2) return ducts from several rooms, 3) central return, 4) any combination of the above. When a cooling coil is not installed it is recommended that the supply duct have an access panel so the heat exchanger can be viewed.
  • Page 12: Electrical Supply

    FURNACE AND RETURN DUCTWORK. THE FLOOR OR PLATFORM MUST PROVIDE SOUND PHYSICAL SUPPORT FOR THE FURNACE WITHOUT CRACKING, GAPS, SAGGING ETC. AROUND THE BASE AS TO PROVIDE A SEAL BETWEEN THE SUPPORT AND THE BASE. FAILURE TO PREVENT PRODUCTS OF COMBUSTION FROM ENTERING THE RETURN SUPPLY...
  • Page 13: Rating The Furnace

    Interconnecting wiring must be secured and protected from damage or disconnection. The use of solderless connectors or equivalent is recommended. The low voltage control wiring exiting the furnace is labeled "thermostat wiring". SETTING THE HEAT ANTICIPATOR The following method should be used in measuring the amp draw of the control circuit to assure proper adjustment of the thermostat...
  • Page 14: Timing The Gas Meter

    6,000 7,000 The input to the furnace must be checked AFTER reorificing. For altitudes above 7,000 feet refer to appropriate section of the National Fuel Gas Code, ANSI Z223.1. To calculate the input of the furnace for installations in altitudes over 2,000 feet, use the following formula;...
  • Page 15: Safety Controls

    • If necessary, adjust the manifold pressure at the gas valve by removing the regulator cap and turning the adjustment screw clockwise to raise the pressure and counterclockwise to reduce the pressure. The manifold pressure must be between 3.2" W.C. and 3.8" W.C. for natural gas and 9.5"W.C.
  • Page 16 MAIN LIMIT SWITCH The main limit switch is a 1/2" disc designed to shut off the burner gas should the outlet (bonnet) temperature exceed the maximum design outlet air temperature. This switch is not adjustable. check the operation, block the return air flow through the unit temporarily. The limit switch should function and shut the burner gas off within a few minutes.
  • Page 17: Circulating Air Filters

    INTEGRATED FAN / IGNITION CONTROL This furnace is equipped with a combination ignition module and fan control. An electronic device ignites the burners upon a call for heat. It also controls the venter blower and the various speed selections of the circulating air blower.
  • Page 18 • Measure the outlet air temperature at a point approximately twelve to eighteen (12 -18) inches from the supply air duct opening of the furnace. It may be necessary to measure the outlet air at several places to obtain an accurate average.
  • Page 19: Removing An Existing Appliance

    • The vent pressure switch will close when it detects a pressure in excess of it's setting. If the pressure switch fails to close the status light will flash three (3) times. The sequence cannot continue until the pressure switch closes. •...
  • Page 20 building. Turn on clothes dryers and any other appliance not connected to the venting system. Turn on any exhaust fans such as range hoods and bathroom exhausts, so they shall operate at their maximum speed. DO NOT operate a summer exhaust fan (whole house fan).
  • Page 21 • Reassemble the furnace in the reverse order. Note: No additional screws or wires are supplied with this product. All components must be reassembled to avoid an unsafe condition. • Reconnect gas supply and check for leaks using a soap solution. If a flexible gas line is used examine it for cracks or weakness.
  • Page 22: Humidifier Control

    ELECTRONIC AIR CLEANER CONTROL The red-capped terminal on the ignition control marked "EAC" is to supply 115 VAC to an Electronic Air Cleaner. This terminal is powered in both the heating and air conditioning modes when the circulating blower is operating. HUMIDIFIER CONTROL The screw terminal...
  • Page 23 DOWNFLOW RIGHT SIDE UPFLOW RIGHT SIDE I II I II I II I II HORIZONTAL LEFT HORIZONTAL RIGHT IO-151...
  • Page 24: Lighting Instructions

    LIGHTING INSTRUCTIONS These instructions are also on the furnace WARNING: Improper AiI-mg installation, adjustm- If you do not follow these instructions exactly, ent, alteration, service a fire or explosion may result causing property or maintenance damage, personal injury or loss of life. cause injury or prop- erty damage.
  • Page 25: Wiring Diagrams

    0"1 FROM FURNACE CHS, q SIS (ROUND POv', E R SUPPL CONDENSING <, UNIT T' STAT ' ..-..TWIN I[}BRI HEaT SOOL IDBR2 HSIR "k P,J'_' ¢/ FUSE IDBR2 P',,R HSIR ,f--\ IDBR/ HIGH WIRING CODE NOTES: [}}(}('f SWITBH FACTORY WIRING REPLACEMENT WIRE MUST...

This manual is also suitable for:

Gmpn060Gmpn080Gmpn120Gmpn040

Table of Contents