Viessmann VITOLADENS 300-W Technical Manual page 33

Wall mounted oil condensing boiler oil condensing storage combi boiler
Table of Contents

Advertisement

Installation accessories
Determining the required internal diameter
5.0
2.5
2.0
1.5
1.0
0.5
0.2
0.1
Mixer control characteristics
A Divicon with three-way mixer
The identified operating ranges B to D provide optimum control
characteristics with the Divicon mixer:
B Divicon with three-way mixer (R ¾)
3
Application range: 0 to 1.0 m
Example:
Heating circuit for radiators with an output of ² = 11.6 kW
Heating system temperature 75/60 °C (ΔT = 15 K)
c Specific heat capacity
µ Mass flow rate
² Output
´ Flow rate
Bypass valve
Part no. 7464 889
To hydraulically balance the heating circuit with mixer. Inserted into
the Divicon.
VITOLADENS 300-W/VITOLADENS 333-F
(cont.)
A
B
C
D
/h
1
3
5
10
20 30 40
Heating circuit output
in kW
C Divicon with three-way mixer (R 1)
3
Application range: 0 to 1.5 m
D Divicon with three-way mixer (R 1¼)
3
Application range: 0 to 2.5 m
Wh
² = µ · c · ΔT
c = 1.163
kg · K
11600 W · kg · K
²
´ =
=
c · ΔT
1.163 Wh · (75-60) K
Select the smallest possible mixer within the application range with
value ´.
Result of this example: Divicon with three-way mixer (R ¾)
Overflow valve
Part no. 7429 738: R ¾
Part no. 7429 739: R 1
Part no. 7429 740: R 1¼
Only with manually controlled heating circuit pump. Fitted onto the
Divicon.
5.0
2.5
2.0
1.5
1.0
0.5
0.2
0.1
/h
/h
´ (1 kg ≈ 1 dm³)
µ
kg
= 665
0.665
h
h
VIESMANN
33
4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitoladens 300-f

Table of Contents