4. Control Specification
4.1
Mode Hierarchy
Outline
Air conditioner control has normal operation mode, forced operation mode, and power transistor
test mode for installation and servicing.
Detail
Cooling Only Model
Heat Pump Model
Note:
Determine Operation Mode
The system judges the operation mode command which is set by each room in accordance with
the procedure, and determines the operation mode of the system.
The following procedure is taken when the modes conflict with each other.
∗1. The system follows the mode which is set first. (First-push, first-set)
∗2. For the rooms where the different mode is set, standby mode is activated. (The operation
lamp blinks.)
Function and Control
Air conditioner control mode
Forced operation mode
Forced cooling operation (for pump down operation)
Wiring error check operation
Power transistor test mode
Normal operation mode
Fan
Cooling (includes drying)
Stop (indoor unit: OFF)
Air conditioner control mode
Forced operation mode
Forced cooling operation (for pump down operation)
Forced heating operation
Wiring error check operation
Power transistor test mode
Normal operation mode
Fan
Cooling (includes drying)
Heating
Stop (indoor unit: OFF)
Unless specified otherwise, a dry operation command is regarded as cooling operation and
a radiant operation command is regarded as heating operation.
Indoor fan operation cannot be made in multiple indoor units. (A forced fan command is
made during forced cooling operation.)
Preheating operation
Discharging from capacitor
Stop
Heating
Defrosting
Preheating operation
Discharging from capacitor
Stop