Control Specification; Mode Hierarchy - Daikin D Series Service Manual

Inverter pair wall mounted type, cooling only, heat pump
Hide thumbs Also See for D Series:
Table of Contents

Advertisement

SiEBE04-507

3. Control Specification

3.1

Mode Hierarchy

Outline
There are two modes; the mode selected in user's place (normal air conditioning mode) and
forced operation mode for installation and providing service.
Detail
1. For heat pump model
2. For cooling only model
Note:
Unless specified otherwise, an indoor dry operation command must be regarded as cooling
operation.
Function and Control
There are following modes; stop, cooling (includes drying), heating (include defrosting)
Air conditioner control mode
Forced operating mode
Forced cooling (for Pump Down Operation)
Normal operating mode
Cooling
Heating
Defrosting
Stop mode (except for cooling/heating modes by indoor command)
Preheat operation
During C (capacitor) is discharging
Stop
There are following models; stop and cooling (including drying).
Air conditioner control mode
Forced operating mode
Forced cooling (for Pump Down Operation)
Normal operating mode
Cooling
Stop mode (except for cooling modes by indoor command)
Preheat operation
During C (capacitor) is discharging
Stop

Control Specification

(R2829)
(R2830)
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents