All electrical work must be carried
out by a suitably qualified and
competent person in accordance
with local and national safety
regulations (BS 7671 in the UK).
– We recommend connecting the
machine to the power supply via a
suitable plug and socket which must
be easily accessible for servicing
and maintenance work after the
machine has been installed.
– For hard-wired machines, connection
should be made via a suitable mains
switch with all-pole isolation which
when in the off position ensures a
3 mm gap between all open
contacts.
– For extra safety and protection we
recommend connecting the machine
by a 30 mA residual current device
(RCD).
– An electrical safety test must be
carried out after installation and after
any service work.
– Check that the phase rotation is
correct when connecting the
machine. Failure to do so could have
an adverse effect on the circulation
pump and impair the wash quality.
– Equipotential bonding should be
carried out.
– For technical data see data plate or
wiring diagram supplied.

Electrical connection

The machine must only be operated
with the voltage, frequency and fusing
shown on the data plate.
Further notes on electrical
connection are given on the
Installation diagram supplied with
the machine.
The data plate showing relevant test
marks is located on the cover located
behind the service panel on the
unclean side of the machine.
The wiring diagram is supplied with
the machine.
WARNING
THIS APPLIANCE MUST BE
EARTHED
73