No.
Part name
Fan,
5
Fan case,
Shaft,
Bearing
SVM-13050.indb 87
SVM-13050.indb 87
Procedure
Quantity of fan
Model
QTY
56
2
Fan motor both sides
80
3
One of shafts are bearings.
The shaft middle part is
110
160
4
supported in the bearing.
1. Detachment
NOTE
It explains the following content by
110 to 160 type.
1) The hanging claw on both sides of fan
case (under) is removed.
2) Fan case (under) is pulled out from
the partition plate, and fan case (under)
is removed.
3) The bolt (2 pcs.) that is the fixing of
the bearing is removed, and the bearing
is removed from the main body.
(Ø8 x 15, 2 pcs.)
4) The screw with the hexagonal screw
hole to of the coupling is loosened,
and the shaft is removed with the fan.
5) The screw with the hexagonal screw
hole of the fan is loosened, and the fan
is detached from the shaft.
2. Attachment
1) The fan is installed in the shaft so that
the tightening screw may come at the
right of the fan toward the heat
exchanger.
2) Insert the fan in the shaft while adjusting
to match the installation mark to the
groove of the fan.
The fan and the screw tightening of the
shaft are the last work.
Refer to the photograph for the direction
of the installation of the fan.
Installation
Heat exchanger side
– 87 –
FILE NO. SVM-13050
Remarks
Hanging claw
Bolt
Groove of the fan
Shaft
Partition plate