Toshiba RAV-SM567CTP-E Service Manual page 86

Air-conditioner split type
Hide thumbs Also See for RAV-SM567CTP-E:
Table of Contents

Advertisement

No.
Part name
3
Electric parts
box
Control P.C.
4
board
SVM-13050.indb 86
SVM-13050.indb 86
Procedure
1. Detachment
1) Perform works of 1 of
2
.
2) Remove the screws of electric parts
box.
3) Draws out forward after the electric
box is moved in the direction of the
arrow, and the back of the part electric
part boxis hung on the edge of the
main body.
2. Attachment
1) It moves in the direction opposite to
time when the electric parts box is
removed and the claw part in the
interior of the electric part box is
inserted in the hanging part of the
main body.
2) Fix the electric parts box by tightening
with screws. (Ø4 x 10, 2 pcs.)
1. Detachment
1) Perform works of 1 of
.
3
2) Remove the indoor/outdoor connecting
wire and remote controller wire from
each terminal block.
3) Remove the connectors which
connected from the control P.C. board
to other parts.
NOTE
First unlock the housing and then
remove the connectors.
CN501 : Louver motor (20P, White)
CN41 : Remote controller terminal block
(2P, Blue)
CN67 : Power supply terminal block
(3P: Black)
CN101 : TC sensor (2P: Black)
CN102 : TCJ sensor (2P, Red)
CN104 : Room temperature
(2P, Yellow)
CN210 : Fan motor (7P, White)
4) Unlock the card edge spacers
(4 positions) in the electric parts box
to remove the control P.C. board.
2. Attachment
1) Attach the electric parts box and
then perform wiring as original.
NOTE
Check there is no missing or contact
failure on the connectors.
– 86 –
FILE NO. SVM-13050
Remarks
Screws
6/6/13 8:52 AM
6/6/13 8:52 AM

Advertisement

Table of Contents
loading

Table of Contents