Toshiba RAV-SM567CTP-E Service Manual page 63

Air-conditioner split type
Hide thumbs Also See for RAV-SM567CTP-E:
Table of Contents

Advertisement

DN
01
Filter sign lighting time
02
Filter pollution leve
03
Central control address
06
Heating suction temperature shift
0F
Cooling only
10
Type
11
Indoor unit capacity
12
System address
13
Indoor unit address
14
Group address
19
Louver type (wind direction adjustment)
Temperature range of cooling/heating
1E
automatic SW control point
28
Power failure automatic recovery
2b
Thermo output SW (T10
31
Ventilation fan (standalone)
32
Sensor SW (Selection of static pressure)
5d
High ceiling SW
60
Timer setting (wired remote controller)
Demand setting
C2
(outdoor unit current demand)
d0
Remote controller operation save function
d3
Rotation number of the self-clean operation
d1
Frost protection function
F6
Presence of Application control kit
Setting data
0007
SVM-13050.indb 63
SVM-13050.indb 63
Table 1. Setting data (CODE No. table (example))
Item
3
)
Table 2. Type: CODE No. 10
Type
Ceiling Type
Setting data
Depending on Type
0000: standard
0099: Not determined
0002: +2°C
(flooring installation type: 0)
0000: Heat pump
Depending on model type
Depending on capacity type
0099: Not determined
0099: Not determined
0099: Not determined
Depending on Type.
Depending on Type.
0000: None
0000: Thermo ON
0000: Not available
0000: Body sensor
0000: Standard
0000: Available
0075: 75 %
0001: Enable
0000: None
0000: None
0000: None
Indoor unit capacity: CODE No. 11
Type name abb.
Setting data
RAV-SM∗∗∗CTP∗
∗ EEPROM initial value on the P .C. board
for indoor unit servicing.
– 63 –
FILE NO. SVM-13050
Factory-set value
Table 3.
Type
0000∗
Disable
0006
40
0007
45
0009
56
0012
80
0015
110
0017
140
0018
160
6/6/13 8:52 AM
6/6/13 8:52 AM

Advertisement

Table of Contents
loading