8-1. Indoor Unit
8-1-1. Test Run Setup on Remote Controller
<Wired remote controller>
TEST
1. When pushing
ON / OFF
Then push
• "TEST" is displayed on LC display during operation of Test Run.
• During Test Run, temperature cannot be adjusted but air volume can be selected.
• In heating and cooling operation, a command to fix the Test Run frequency is output.
• Detection of error is performed as usual. However, do not use this function except case of Test Run
because it applies load on the unit.
2. Use either heating or cooling operation mode for [TEST].
NOTE : The outdoor unit does not operate after power has been turned on or for approx. 3 minutes after
operation has stopped.
3. After a Test Run has finished, push
(To prevent a continuous test run operation, 60-minutes timer release function is provided to this remote
controller.)
<Wireless remote controller>
SVM-13050.indb 64
SVM-13050.indb 64
8. SETUP AT LOCAL SITE AND OTHERS
button on the remote controller for 4 seconds or more, "TEST" is displayed on LC display.
button.
TEST
button again and check that [TEST] on LC display has gone off.
Screw
Signal receiving unit
Lower cace
SW30
DIP switch [SW30]
4
ON=follower OFF=header
3
ON=B
OFF=A
2
Not used
1
Not used
SW30
ON
1
2
3
4
– 64 –
FILE NO. SVM-13050
6/6/13 8:52 AM