Toshiba RAV-SM567CTP-E Service Manual page 48

Air-conditioner split type
Hide thumbs Also See for RAV-SM567CTP-E:
Table of Contents

Advertisement

[E04 error]
Does outdoor operate?
YES
Check indoor P.C. board.
Defect → Replace
SVM-13050.indb 48
SVM-13050.indb 48
NO
Is group address setup of
remote controller correct?
YES
Are wiring in indoor unit and
1, 2, 3 inter-unit cables correct?
YES
Are wirings of terminal blocks
(1, 2, 3) wired to CN04 normal?
YES
Does D502 (Orange LED) flash
after power supply turned on again?
YES
Check outdoor P.C. board.
Defect → Replace
– 48 –
FILE NO. SVM-13050
NO
Check CODE No. [14].
NO
Correct wiring and
inter-unit cables.
NO
Correct wiring of connector
and terminal blocks.
Check indoor P.C. board.
NO
(MCC-1643)
Defect → Replace
∗ As shown in the following figure,
carry out measurement within 20 seconds
after the power was turned on.
S5277G
Black
3
White
2
1
Terminal block
6/6/13 8:52 AM
6/6/13 8:52 AM