Superior DRT4040DMN Installation And Operation Instruction Manual page 23

Superior drt40 series direct vent gas fireplaces
Table of Contents

Advertisement

Innovative Hearth Products
Superior
DRT40 Direct Vent Gas Fireplace
TM
HORIZONTAL VENT FIGURES/TABLES (continued)
H 1
Wall Firestop/
Spacer
SV4.5HF**
V
Square termination (SV4.5HT-2) shown.
Figure 40 - Rear Vent - TWO 90 DEGREE ELBOWS
Wall Firestop/Spacer
H 1
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
Square termination (SV4.5HT-2) shown.
See Table 8 on Page 22 as an aid in venting component
selection for a particular range of exterior wall thicknesses.
Figure 41 - Top Vent - TWO 90 DEGREE ELBOWS
H
Ceiling
Firestop/Spacer
SV4.5VF*
*When using Secure Flex , use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
SV4.5HF**
H
Wall Firestop/Spacer
SV4.5HF**
Ceiling Firestop/Spacer
SV4.5VF*
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
H
Maximum
+H
1
feet
(meters)
(1.524)
5
(3.048)
10
(4.572)
15
(6.096)
20
H + H 1 = 20 feet (6.096 meters) Max.
Example: If 20 feet of (H) horizontal vent run is needed,
then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of
(V) vertical, you are allowed 5 feet of (H) horizontal run,
up to a maximum horizontal run of 20 feet.
®
See Table 8 on page 22 as an aid in venting component
selection for a particular range of exterior wall thicknesses.
V
Installation and Operation Instructions
TABLE H
H Maximum
V Minimum
(meters)
feet
feet
2
(0.610)
1
4
(1.219)
2
6
(1.829)
3
8
(2.438)
4
V + H + H 1 = 40 feet (12.2 m) Max.
H = 8 feet (2.438 meters) Max.
TABLE J
H
Maximum
V Minimum
+ H
1
feet
(meters)
feet
(0.914)
Elbow Only
3
(1.524)
5
1
(3.048)
10
2
(4.572)
15
3
20
(6.096)
4
H
V +
+ H
= 40 feet (12.2 m) Max.
1
H
+ H
= 20 ft. (6.096 m) Max.
1
Example: If 20 feet of (H) horizontal vent run
is needed, then 4 feet minimum of (V) vertical
vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For
every 1 foot of (V) vertical, you are allowed 5
feet of (H) horizontal run, up to a maximum
horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical
rise except where an elbow is the only vertical
component in the system. See Figure 38.
900357-00, 06/2015
(meters)
(0.305)
(0.610)
(0.914)
(1.219)
(meters)
(0.305)
(0.610)
(0.914)
(1.219)
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Drt4040dmpDrt4045denDrt4040denDrt4045dmnDrt4045dmp

Table of Contents