Toshiba RAS-B10SKVP-E Service Manual page 28

Split type
Hide thumbs Also See for RAS-B10SKVP-E:
Table of Contents

Advertisement

Outdoor Unit : RAS-3M18SACV-E
<Cooling>
Temperature
No. of
condition
operating
units
Indoor
Outdoor
1 unit
2 units
27 /19°C
35 / –°C
3 units
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 meters × 3 units (5m/each indoor unit)
Operating
Standard
combination (Unit)
pressure
P (MPa)
A
B
C
10
0.8 to 1.0
13
0.7 to 0.9
16
0.6 to 0.8
10
10
0.8 to 1.0
13
10
0.8 to 1.0
16
10
0.8 to 1.0
13
13
0.8 to 1.0
10
10
10
0.8 to 1.0
13
10
10
0.8 to 1.0
16
10
10
0.8 to 1.0
13
13
10
0.8 to 1.0
– 28 –
Heat exchanger
Indoor
pipe temp.
fan
(Manual)
T1 (°C)
T2 (°C)
11 to 13
42 to 44
High
8 to 10
46 to 48
High
6 to 8
49 to 51
High
13 to 14
48 to 50
High
13 to 14
48 to 50
High
13 to 14
48 to 50
High
13 to 14
48 to 50
High
16 to 18
48 to 50
High
16 to 18
48 to 50
High
16 to 18
48 to 50
High
16 to 18
48 to 50
High
Compressor
Outdoor
revolution
fan
(rps)
MED
32
MED
52
MED
75
MED
63
MED
63
MED
65
MED
65
MED
62
MED
62
MED
62
MED
62